Display Functions - Eaton 9PX1000IRT2U-L Advanced User's Manual

Table of Contents

Advertisement

Table 4. LCD Operating Status (Continued)
Operation status
Battery mode
End of backup time
High Efficiency mode
Bypass mode
2 2 . . 6 6
D D i i s s p p l l a a y y F F u u n n c c t t i i o o n n s s
Press the (
the menu structure. Press the (
previous menu.
Table 5. Display Functions
Main menu
Measurements
Control
Settings
Cause
A utility failure has occured and the UPS
is on Battery mode.
The UPS is on Battery mode and the
battery is running low.
The UPS is operating on High Efficiency
mode.
An overload or a fault has occurred, or a
command has been received, and the
UPS is in Bypass mode.
) button to activate the menu options. use the two middle buttons (
) button to select an option. Press the ESC button to cancel or return to the
Submenu
Go to Bypass
Load segments On/Off
Start battery test
Connectivity test
Function reset
Local settings
Description
The UPS is powering the equipment with
the battery power. Prepare your
equipment for shutdown.
Low Battery Warning settings:
[Capacity] [0%] ... [100%]
[Runtime] [0mn] ... [60mn]
The alarm triggers when the set
percentage of battery capacity or
remaining back-up time is reached.
The UPS is powering and protecting the
equipment
Equipment is powered but not protected
by the UPS.
Display information or Menu function
[Load] W VA A pf / [Input/Output] V Hz /
[Efficiency] % / [Battery] % min V n°
EBM / [Battery remaining life] months /
[Average power usage] Wh / [Cumulated
power] Wh / BMS Information
Transfers the UPS on Bypass mode
Commands the load segments
Starts a manual battery test
Tests dry contact relay outputs and relay
card contacts. Simulates line failure and
battery low
Clears active fault, power usage, battery
remaining life, reset NMC, Restore
factory settings.
Sets product general parameters
Eaton 9PX Lithium-Ion User Guide P-164001006—Rev 03

Display Functions

and
) to scroll through