2. Presentation
In/Out settings
ON/OFF settings
Battery settings
Page 12
Description
Available settings
Load segments
[Disable] [0s] [1 s] [2 s]...[65354 s]
- Auto shutdown
During a power outage,
delay
authorizes UPS to turn off power to
equipment connected to Group 1
and/or Group 2 outlets.
This feature allows the shedding of
non-critical loads in order to conserve
battery power for critical loads
connected to the Primary group.
Overload
[5 %] [10 %] [15 %] [20 %] ... [100 %]
prealarm
[105 %]
Sets critical percentage of load where
alarm overload alarm occurs.
Cold start
[Disable] [Enable]
Authorizes the product to start on
battery power.
Forced reboot
[Disable] [Enable]
If mains recover during a shutdown
sequence:
If set to Enable, shutdown sequence
will complete and wait 10 seconds
prior to restart,
If set to Disable, shutdown sequence
will not complete and restart will
occur immediately.
Auto restart
[Disable] [Enable]
Authorizes the product to restart
automatically when mains recovers
after a complete battery discharge.
Energy saving
[Disable] [Enable]
If Enable, UPS will shutdown after
5 min. of back-up time, if no load is
detected on the output.
Sleep mode
[Disable] [Enable]
If disable, LCD and communication
will turn OFF immediately after UPS
is OFF.
If enable, LCD and communication
stays ON 1h30 min after UPS is OFF.
Remote command
[Disable] [Enable]
If enable, shutdown or restart
commands from software are
authorised.
Automatic battery
[No test] [Every day] [Every week]
test
[Every month]
Available only if battery charge mode
is set to constant charge.
Low battery
[10 %] [20 %] [30 %] [40 %] [50 %]
warning
[60 %] [70 %] [80 %] [90 %]
The alarm triggers when the set
percentage of battery capacity is
reached during a back-up time.
Restart battery
[10 %] [20 %] [30 %] [40 %] [50 %]
level
[60 %] [70 %] [80 %] [90 %] [100 %]
If set, automatic restart will occur
only when percentage of battery
charge is reached.
Battery charge
[ABM cycling] [Constant charge]
mode
EBM number
[0] [1] [2] [3] [4]
setting
Using standard EBM, UPS detects
automatically the amount of EBM
connected.
Deep discharge
[Yes] [No]
protection
If set to Yes, the UPS automatically
prevents battery from deep discharge
by adapting end of back-up time
voltage threshold.
Default settings
Group 1: Disable
Group 2: Disable
[105 %]
Enable
Enable
Enable
Disable
Disable
Enable
Every week
(in constant charge)
otherwise following ABM
20 %
0 %
ABM cycling
EBM automatic detection,
otherwise 0
Yes
614-03797-00_EN