Toshiba RAV-SM304SDT-TR Service Manual page 96

Table of Contents

Advertisement

[E03 error] (Master indoor unit)
[E03 error] is detected when the indoor unit cannot receive a signal from the remote controller
(also central controller).
Check A and B remote controllers and communication lines of the central control system U3 and U4.
As communication is impossible, this check code [E03] is not displayed on the remote controller and the central
controller. [E01] is displayed on the remote controller and [C06 error] is displayed on the central controller.
If these check codes generate during operation, the air conditioner stops.
[F29 error]
This check code indicates a detection error of IC10 non-volatile memory (EEPROM) on the indoor unit P.C.
board, which generated during operation of the air conditioner. Replace the service P.C. board.
∗ When EEPROM was not inserted when power supply turned on or when the EEPROM data read/write
operation is impossible at all, the automatic address mode is repeated. In this time, [97 error] is displayed on
the central controller.
(Approx.
3 minutes)
[SET] is displayed
(Power ON)
on remote controller.
[P31 error] (Follower indoor unit)
When the master unit of a group operation detected [E03], [L03], [L07] or [L08] error, the follower unit of the
group operation detects [P31 error] and then the unit stops.
There is no display of the check code or alarm history of the remote controller. (In this model, the mode enters
in automatic address set mode when the master unit detected [L03], [L07] or [L08] error.)
(Approx.
1 minute)
[SET]
goes off.
(Repetition)
– 96 –
LED (D02) on indoor unit
P.C. board flashes with
1Hz for approx. 10 seconds.
Reboot
(Reset)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents