Toshiba RAV-SM304SDT-TR Service Manual page 94

Table of Contents

Advertisement

[F02 error]
Is connection of TC sensor connector
(CN101 on Indoor P.C. board) correct?
YES
Are characteristics of
TC sensor resistance value normal?
YES
Check indoor P.C. board (MCC-1570).
Defect → Replace
[F01 error]
Is connection of TCJ sensor connector
(CN102 on Indoor P.C. board) correct?
YES
Are characteristics of
TCJ sensor resistance value normal?
YES
Check indoor main P.C. board (MCC-1570).
Defect → Replace
NO
NO
∗ Refer to Characteristics-2.
NO
NO
∗ Refer to TCJ sensor
(Temperature-Resistance value characteristic table)
Correct connection of connector.
Correct connection of connector.
– 94 –
Replace TC sensor.
Replace TCJ sensor.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents