Toshiba RAV-SM304SDT-TR Service Manual page 117

Table of Contents

Advertisement

DN
01
Filter sign lighting time
02
Filter pollution leve
03
Central control address
06
Heating suction temperature shift
OF
Cooling only
10
Type
11
Indoor unit capacity
12
System address
13
Indoor unit address
14
Group address
Temperature range of cooling/heating
1E
automatic SW control point
28
Power failure automatic recovery
2A
Option/Abnormal input (CN70) SW
2b
Thermo output SW (T10
31
Ventilation fan (standalone)
32
Sensor SW (Selection of static pressure)
40
Humidifier control (+ drain pump control)
5d
External static pressure
60
Timer setting (wired remote controller)
Demand setting
C2
(outdoor unit current demand)
d0
Remote controller operation save function
d1
Frost protection function
Table 2. Type: CODE No. 10
Setting data
Type
0005
Slim Duct Type
Table 1. Setting data (CODE No. table (example))
Item
)
Type name abb.
RAV-SM∗∗∗SDT-E
∗ EEPROM initial value on the P.C. board for indoor unit servicing.
Setting data
Depending on Type
0000: standard
0099: Not determined
0002: +2°C
(flooring installation type: 0)
0000: Heat pump
Depending on model type
Depending on capacity type
0099: Not determined
0099: Not determined
0099: Not determined
0003: 3 deg (Ts ± 1.5)
0000: None
0002: Humidifier
0000: Thermo ON
0000: Not available
0000: Body sensor
0003: Humidifier ON + Pump OFF
0000: Standard (10Pa)
0001: High static pressure 1 (20Pa)
0003: High static pressure 2 (35Pa)
0006: High static pressure 3 (50Pa)
0000: Available
0075: 75 %
0001: Enable
0000: None
Table 3. Indoor unit capacity: CODE No. 11
Setting data
0000*
0003
0006
0007
0009
0012
0015
0017
0018
– 117 –
Factory-set value
Type
Disable
30
40
45
56
80
110
140
160

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents