Toshiba RAV-SM304SDT-TR Service Manual page 55

Table of Contents

Advertisement

No.
Item
6
Air speed
selection
(Continued):
In case of
Slim Duct Type
Outline of specifications
Slim Duct Type
Standard
Item code
[5d]
0
SW501 (1)/(2)
OFF/OFF
Tap
HEAT COOL HEAT COOL HEAT COOL HEAT COOL
F1
F2
F3
F4
F5
F6
F7
HH
HH
F8
F9
H+
H+
FA
H
H
FB
L+
L+
FC
L
L
FD
LL
LL
Slim Duct Type
SM30
Tap
F1
1240
F2
1140
F3
1120
F4
1020
F5
1020
F6
1000
F7
950
F8
910
F9
900
FA
830
FB
800
FC
740
FD
550
3) In heating operation, the mode changes to [UL] if
thermostat is turned off.
4) If Ta ≥ 25°C when heating operation has started and when
defrost operation has been cleared, the air conditioner
operates with (H) mode or higher mode for 1 minute after
Tc entered in E zone of cool air discharge preventive
control (Item 7).
Type 1
Type 3
1
3
ON/OFF
OFF/ON
HH
HH
HH
H+
HH
HH
H+
H+
H
H
H+
H+
H
H
L+
L+
L+
L+
LL
LL
LL
LL
SM40
SM45
Revolution speed (rpm)
1260
1260
1180
1180
1120
1120
1040
1040
1020
1020
990
990
960
960
950
950
910
910
870
870
840
840
790
790
550
550
– 55 –
Remarks
Selection of high static
Type 6
pressure type
6
Item code:
ON/ON
[5d] or selection of high
static pressure on P.C.
board SW501
HH
H+
H
H
L+
L+
LL
LL
SM56
1320
1220
1220
1220
1180
1180
1180
1040
990
990
880
820
550

Hide quick links:

Advertisement

Table of Contents
loading