In Case of Indoor Unit Connect With Inverter Multi System (IMS)

Connecting cable
Connecting cable
connect to L 2 3
Terminal block (L N 1 2 3)

Power supply input Wiring Diagram for Inverter Multi System (IMS)

Power input at Outdoor Terminal Block
Indoor
Terminal
Block
Outdoor
Terminal
Block
1. The power supply must be same as the rated of air conditioner.
2. Prepare the power source for exclusive use with air conditioner.
3. Circuit breaker must be used for the power supply line of this air conditioner.
4. Be sure to comply power supply and connecting cable for size and wiring method.
5. Every wire must be connected f rmly.
6. Perform wiring works so as to allow a general wiring capacity.
7. Wrong wiring connection may cause some electrical part burn out.
8. Incorrect or incomplete wiring is carried out, it will cause an ignition or smoke.
9. This product can be connected to main power supply.
Connection to fixed wiring : A switch which disconnects all poles and has a contact separation at least 3mm must be
incorporated in the fixed wiring.
Power Supply Input at Outdoor Unit Terminal Block
Indoor Unit
Stripping length of the
Connecting cable
50 mm
10 mm
3
2
L
10 mm
70 mm
Earth line
Connecting cable
Power input
CAUTION
- 73 -
FILE NO. SVM-19001
Outdoor Unit
Terminal block
1(L)
Earth line
Connecting cable
Earth line
Connecting cable
Chassis
Chassis
Power cord
Earth line
Power cord