10-4. Outdoor Unit
10-4-1. Installation place
• A place which provides the spaces around the
outdoor unit as shown in the diagram
• A place which can bear the weight of the outdoor
unit and does not allow an increase in noise level
and vibration
• A place where the operation noise and discharged
air do not disturb your neighbors
• A place which is not exposed to a strong wind
• A place free of a leakage of combustible gases
• A place which does not block a passage
• When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
• The allowable length of the connecting pipe.
RAS-05, 07, 10,
Model
Chargeless
Maximum length
Additional
refrigerant charging
• The allowable height of outdoor unit installation site.
RAS-05, 07, 10,
Model
Maximum height
• A place where the drain water does not raise any
problems
CAUTION
When the outdoor unit is installed in
a place where the drain water might cause
any problems, Seal the water leakage
point tightly using a silicon adhesive or
caulking compound.
10-4-2. Precautions about Installation in Regions
with Snowfall and Cold Temperatures
Do not use the supplied drain nipple for draining water.
Drain the water from all the drain holes directly.
To protect the outdoor unit from snow accumulation,
install a holding frame, and attach a snow protection
hood and plate.
Do not use a double-stacked design.
RAS-16, 18J2AVG-E
13J2AVG-E
Up to 15 m
Up to 15 m
15 m
20 m
-
16 - 20 m (20 g / 1 m)
RAS-16, 18J2AVG-E
13J2AVG-E
12 m
12 m
Front
Anchor
bolts

Precautions for adding refrigerant

• Use a scale having a precision with at least 10 g
per index line when adding the refrigerant.
Do not use a bathroom scale or similar instrument.
• Use liquid refrigerant when refilling the refrigerant.
Since the refrigerant is in liquid form, it can fill quickly.
Therefore, perform the filling operation
carefully and insert the refrigerant gradually.
CAUTION
1. Install the outdoor unit without anything blocking
the air discharging.
2. When the outdoor unit is installed in a place
exposed always exposed to strong wind like a
coast or on a high storey of a building, secure
the normal fan operation using a duct or a wind
shield.
3. In particularly windy areas, install the unit such
as to avoid admission of wind.
4. Installation in the following places may result in
trouble.
Do not install the unit in such places.
• A place full of machine oil.
• A saline-place such as the coast.
• A place full of sulfide gas.
• A place where high-frequency waves are likely
to be generated as from audio equipment,
welders, and medical equipment.
- 66 -
FILE NO. SVM-19001
Snow protection plate
Install at least 50 cm
Snow protection hood
above the snow
accumulation line.
At least
50 cm
Snow accumulation line
Holding frame
Fig. 10-4-1