The horizontal flue MUST be installed under a 3° fall towards the boiler (50 mm per
metre) and MUST be supported with a minimum of 1 bracket at each meter length.
Best recommended position of the bracket is just before the joint.
INFORMATION
Flexible flue gas lines may NOT be used in horizontal connection sections.
INFORMATION
The maximum lengths in the table below apply to each gas boiler separately.
C
(6)
83
Twin-80
L1+L2 (m)
80
Special remark regarding C
the combined gas exhaust system.
Number of units
2
3
4
5
6
7
8
9
10
11
12
L1
L1
C
43
C
43
5
5
L1
L1
L2
C
43
C
43
5
5
60/100
80/125
L1 (m)
10
: See the table below for the minimum diameters of
83
7
Installation
|
C
(5)
43
Twin-80
L1 (m)
L1+L2 (m)
29
80
Minimum Ø
130
150
180
200
220
230
250
270
280
290
300
Installer reference guide