8
|
Configuration
Parameter
Setting
Installation type
Space heating pump
continuous
Maximum space heating
power set
.
Maximum capacity space
heating pump
Maximum domestic hot water
power set
(not applicable for
Switzerland)
Minimum supply temperature
of the heat curve
.
Maximum supply temperature
of the heat curve
Minimum outside
temperature of the heat curve
Installer reference guide
142
Range
Default
settings
0~3
0~3
~85%
70%
~100%
100%
10°C~25°C
15°C
30°C~90°C
90°C
–30°C~10°C
–7°C
Description
0
0=Combi
1=Heating only + external
domestic hot water tank
2=Domestic hot water only
(no heating system required)
3=Heating only
It is recommended not to
modify this setting.
0
0=Post purge period only
1=Pump continuously active
2=Pump continuously active
with MIT switch
3=Pump on with external
switch
This setting has no effect.
Maximum power in heating.
This is a percentage of the
maximum set in parameter .
We strongly recommend not
modifying this setting.
80
There is no space heating
pump in the gas boiler.
Changing this setting has no
effect.
Maximum power in instant
domestic hot water. This is a
percentage of the maximum
set in parameter . Because of
the 2-digit display, the highest
displayable value is 99. It is
however possible to set this
parameter to 100% (default
setting). We strongly
recommend not modifying this
setting.
Do NOT modify this setting on
the boiler. Use the user
interface instead.
Do NOT modify this setting on
the boiler. Use the user
interface instead.
Do NOT modify this setting on
the boiler. Use the user
interface instead.
CHYHBH05+08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10