To perform a manual air purge
CHYHBH05+08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10
Air purge prerequisites
3
Install air purges on each part of the installation where the pipe work goes
down. (For example on a tank with connections on top.)
4
Fill the circuit to ±2 bar.
5
Purge all radiators and all other air purges installed on the circuit.
6
Repeat steps 2 and 3 until purging the radiators and the other points does NOT
longer lead to a pressure drop.
7
Make sure that the leaving water temperature home page, room temperature
home page, and domestic hot water home page are turned OFF.
When an air bubble blocks the pump and there is no flow, a 7H error can occur. In
this case, stop the air purge function and restart the operation. This will cause the
bubble to leave the pump. Make sure the pressure in the circuit is ±2 bar and refill
if necessary.
To check if the air purge function is finished, monitor the flow rate. If it stays
constant when the pump is running at high or low speed, the unit is properly
purged. To monitor the flow rate, go to [6.1.8].
The air purge function automatically stops after 42 minutes.
INFORMATION
For best results, air purge each loop separately.
Prerequisite: Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1 Set the user permission level to Installer. See
4
to
Installer" [
 104].
2 Set the air purge mode: go to [A.7.3.1]
Commissioning > Air purge > Type.
3 Select Manual and press
4 Go to [A.7.3.4]
purge > Start air purge and press
Result: The manual air purge starts and the following screen appears.
Air purge
Flow rate
0.5
l/min
Speed
Low
Circuit
SHC
Bypass
Yes
Stop
Adjust
5 Use the and buttons to scroll to Speed.
6 Use the and buttons to set the desired pump speed.
Result: Low
Result: High
7 If applicable, set the desired position of the 3-way valve (space heating/
domestic hot water). Use the and buttons to scroll to Circuit.
8 Use the and buttons to set the desired position of the 3-way valve.
Result: SHC or Tank
9 Set the desired position of the bypass valve. Use the and buttons to scroll to
Bypass.
.
> Installer
settings > Commissioning > Air
to start the air purge function.
01:18
Tue
Scroll
10
Commissioning
|
"To set the user permission level
> Installer
settings >
Installer reference guide
157