7
|
Installation
Installer reference guide
72
NOTICE
It is recommended to install shut-off valves to space heating in and space heating
out connections. Shut-off valves are field supplied. They allow service to the unit
without draining the whole system.
Foresee a drain/fill point to drain or fill the space heating circuit
NOTICE
Do NOT install valves to shut down the entire emitter system (radiators, floor heating
loops, fan coil units, ...) instantly if this can result in an immediate short circuit of the
water flow between the outlet and the inlet of the unit (for example via a bypass
valve). This may trigger an error.
1 Connect the water inlet connection (Ø22 mm).
2 Connect the water outlet connection (Ø22 mm).
b
a
a Water inlet
b Water outlet
3 In case of connection with the optional domestic hot water tank, see the
installation manual of the domestic hot water tank.
NOTICE
Install air purge valves at all local high points.
NOTICE
In case an optional domestic hot water tank is installed: A pressure relief valve (field
supply) with an opening pressure of maximum 10 bar (= 1 MPa) must be installed on
the domestic cold water inlet connection in accordance with the applicable
legislation.
CHYHBH05+08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10