ON-SITE MEASUREMENT OF THE
COMBUSTION EFFICIENCY
3.9.1

ENABLE THE CALIBRATION FUNCTION

ATTENTION!
Function reserved exclusively to Authorised Service
Centres.
1 - SELECTION
Press ''B'' and use the knob ''C'' to select the symbol
2 - Calibration function SELECTION
using knob ''C'' and confirm by pressing key A (enter the
Set
access code).
Instructions for the installer
3 - MAXIMUM/MINIMUM POWER
Use knob ''C'' and set to
Confirm using key '' A '' in order to display
Use knob ''C'' and set to
Confirm using key "A"
Use knob "C" to adjust the power that is to be calibrated, confirming
with key "A".
• MINIMUM POWER
• MAXIMUM POWER
Calibrate each heating element by selecting the burners:
.
4 - DEACTIVATION
After calibrating, press ''B'' to go back to the main menu.