Error
Anomaly signalled
Code
Combustion signal
93
beyond limit
94
Combustion anomaly
Combustion signal
95
discontinuous
Clogged flue
96
Block - maximum no.
98
of software errors
99
General block
(1) If the shutdown or fault persists, contact an authorised company (e.g. Authorised Service Centre)
(2) The anomaly can only be verified in the list of errors in the "Information" menu
Cause
The combustion signal is beyond the adjustment range re-
quired for a limited period of time.
A problem is detected on the combustion control, which
may be due to: gas low pressure, flue recirculation, defective
gas valve or P.C.B.
The system detects a discontinuous combustion signal.
This occurs in the event an obstruction is detected in the
flue system.
The maximum number of software errors possible has been
reached.
A boiler anomaly has been detected.
Boiler status / Solution
The boiler keeps working (1) (2)
If normal conditions are restored the
boiler restarts without having to be
reset (1) (2)
The boiler keeps working (1) (2)
The boiler does not start (1)
If normal conditions are restored the
boiler restarts without having to be
reset
Press the Reset button (1)
Press the Reset button (1)