System Filling; Filling The Condensate Drain Trap - Immergas VICTRIX OMNIA Instructions And Recommendations

Hide thumbs Also See for VICTRIX OMNIA:
Table of Contents

Advertisement

1.24 WATER TREATMENT PLANT FILLING
As already mentioned in the previous paragraphs, a treatment of
the thermal and domestic system water is required, in compliance
with the local standards in force.
The parameters that influence the duration and proper operation
of the heat exchanger are the water's PH, total hardness, conduc-
tivity, and oxygen, together with the system's processing residues
(any welding residues), any oil present and corrosion products
that can, in turn, cause damage to the heat exchanger.
In order to prevent this from happening, you are recommended
to:
- clean the system with clean water to eliminate solid residues
before installation on new and old systems;
- clean the system with a chemical treatment:
• clean the new system with a suitable cleaning device (for ex-
ample Sentinel X300, Fernox Cleaner F3 or Jenaqua 300)
combined with thorough washing;
• clean the old system with a suitable cleaning device (for ex-
ample Sentinel X400 or X800, Fernox Cleaner F3 or Jenaqua
400) combined with thorough washing;
- Check the maximum total hardness and quantity of filling wa-
ter referring to the graphics (Fig. 34); if the contents and hardc -
ness of the water are below the indicated curve, no specific treat-
ment is required; otherwise, to limit the content of calcium
carbonate, you must provide for water-filling treatment.
- If it is necessary to provide for water treatment, it should be done
through complete desalination of the filling water. As opposed
to the complete softening process, desalinating the water com-
pletely not only removes hardening agents (Ca, Mg), but also
eliminates all other minerals to reduce water-filling conductiv-
ity up to 10 microsiemens/cm. Given its low conductivity, desal-
inated water does not only prevent the formation of lime scale,
but also serves as protection against corrosion.
- Insert a suitable inhibitor / passivator (for example Sentinel
X100, Fernox Protector F1, or Jenaqua 100); if required, also in-
sert appropriate antifreeze (such as for example Sentinel X500,
Fernox Alphi 11 or Jenaqua 500).
- Check electrical conduction of the water, which should be high-
er than 2000 µs/cm in the case of treated water and lower than
600 µs/cm in the case of non-treated water.
- To prevent corrosion, the water system's PH should be between
7.5 and 9.5.
- Check the maximum content of chlorides, which should be less
than 250 mg/l.
For quantities and methods of use of water-treatment
products, refer to the instructions provided by their
manufacturer.
Total water hardness °F
The graph refers to the entire life cycle of the system.
Therefore, also consider scheduled and unscheduled
maintenance, which involves emptying and filling the
said system.

1.25 SYSTEM FILLING

1. Loosen the cap of the automatic vent valve on the circulating
pump.
2. Slightly open the filling cock (Par. 1.6) to ensure release of air
bubbles in the water via the boiler and central heating system
vents.
3. Close the filling cock when the boiler pressure gauge indicates
approx. 1.2 bar.
4. Open the radiator vent valves.
5. Close radiator vent valves when only water escapes from them.
During these operations activate the automatic venting
functions present in the boiler.
1.26 FILLING THE CONDENSATE DRAIN
TRAP
On first lighting of the boiler, flue gas
may come out the condensate drain; after
a few minutes' operation check that this
no longer occurs. If this is the case, the
drain trap is correctly filled with conden-
sate up to a height that does not allow the
flue gas to pass.
34
33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

3.028358

Table of Contents