3.11 QUICK CALIBRATION

This function allows you to calibrate the boiler automatically
without requiring or giving the possibility to alter the parameters.
Typically "fast calibration" is used after having set the type of flue
in menu "F", which once altered causes anomaly "72".
Before carrying out the fast calibration, ensure that all
the requirements indicated in the relevant paragraphs
have been met (Par. 1.25 - 1.26).
No active requests for central heating or D.H.W. produc-
tion must be present and the boiler must not be in
"Stand-by" mode.
In the event of anomaly "72" (Par. 2.5) the boiler cancels any re" -
quests by itself.
The energy produced is dissipated via the heating circuit; alterna-
tively, the energy can be released from the DHW circuit by open-
ing any hot water tap.
In this case the only active temperature control is the
flow probe that limits the maximum temperature
exiting the boiler at 90°C, therefore be careful not to get
burned.
Press and hold buttons "
"
and "
" for more than 5 sec-
onds.
49
The display will show two dash-
es "--" flashing. Now enter the
password "72" to activate fast
calibration.
50
The calibration stages (nominal, intermediate and minimum)
progress automatically and you must wait until calibration is
complete.
,
Press the "
" key to activate
calibration.
Once the function is active, the
boiler sequentially carries out
the procedures required to cali-
brate the appliance with the
51
nominal, intermediate and
minimum heat output values.
At this stage the display fea-
tures flashing icons: "
"
" and the operating tem-
perature is displayed, alternat-
ed with the current operating
heat output.
52
" and