A
B
ADAPTOR
Ducting
(A) mm
Ø 60
66
Rigid
Ø 50
66
Flexible
Ø 80
86
Rigid
Ø 80
90
Flexible
1
12
3
3
4
11
10
The adapter kit includes (Fig. 30):
No.1 Door adaptor Ø 100 or Ø 125 (1)
No.1 Door gasket made of neoprene (2)
No.4 Screws 4.2 x 9 ST (3)
No.1 Hex headed screw M6 x 20 (4)
No.1 Flat nylon washer M6 (5)
No.2 Door hole closure metal-sheet plate plug (6)
No.1 Plug gasket made of neoprene (7)
No.1 Toothed washer M6 (8)
No.1 M6 nut (9)
No.1 (kit Ø 80/125) Concentric gasket Ø 60/100 (10)
No.1 (kit Ø 80/125) Flanged adapter Ø 80/125 (11)
No.4 (kit Ø 80/125) Hexagon-head screws M4 x 16 flat-tip screwdriver
(12)
No.1 (kit Ø 80/125) Bag of lubricating talc
Supplied separately (Fig. 30):
No.1 Ducting kit door (A)
30
A
C
SHAFT
SHAFT
(B) mm
(C) mm
106
126
106
126
126
146
130
150
2
A
9
8
6
7
6
5
Technical data
The dimensions of the shafts must ensure a minimum gap be-
tween the outer wall of the smoke duct and the inner wall of the
shaft: 30 mm for circular section shafts and 20 mm in the event of
a square section shaft (Fig. 29).
Maximum 2 changes of direction are allowed on the vertical sec-
tion of the flue system with a maximum clearance angle of 30°
with respect to the vertical.
The maximum vertical extension using a Ø 60 ducting system is
13 m, the maximum extension includes 1 bend Ø 60/100 at 90°,
1 m of horizontal pipe Ø 60/100, 1 90° ducted bend Ø 60 and the
roof terminal for ducting.
29
To determine the C
described (Fig. 31) one must consider that 1 metre of ducted pipe
according to the indications described has a resistance factor
equal to 4.9.
The maximum vertical extension using a Ø 80 ducting system is
28 m, the maximum extension includes 1 adapter Ø 60/100 to
Ø 80/125, 1 87° bend Ø 80/125, 1 m of horizontal pipe Ø 80/125, 1
90° ducted bend Ø 80 and the roof terminal for ducting.
To determine the C
described (Fig. 31) one must consider the following head losses:
- 1 m of concentric pipe Ø 80/125 = 1 m of ducted pipe;
- 1 87° bend = 1.4 m of ducted pipe;
Consequently one must subtract the equivalent length of the part
added to the 28 m available.
30
flue system in configurations other than that
93
flue system in configurations other than that
93