Control Panels - Pentair HYDROMATIC HPGR200-D Owner's Manual

Submersible grinder pumps
Table of Contents

Advertisement

Available languages

Available languages

Electrical
TABLE I: Motor, Switch, & Cord Specifications
Model
Motor
Number
HP
HPGR200-D
 2
HPGR200-D3
2
HPGR200-D4
2
Factory Connected for 230V/3Ø as shown
Z1
Y1
X1
230 Volt
Power Supply
White
Red
Z1 Y1 X1
U1
V1
Motor
Windings
Figure 2: 230 Volt 3 Phase Wiring Connections
Connect for 460V as shown.
460 Volt
Power Supply
White
Red
W2
V2
U2
Z1
Y1
X1
Z1 Y1
U1
X1
V1
W1
Motor
Windings
Figure 3: 460 Volt 3 Phase Wiring Connections
Motor
Full
Voltage
Load Amps
230/60/1
13.0
230/60/3
8.2
460/60/3
4.1
Z2
Y2
X2
Black
W2
V2
U2
X2 Y2 Z2
W1
Motor
Windings
4355 0303
Black
X2
Y2
V2
U2
W2
X2 Y2 Z2
Motor
Windings
4354 0303
Individual
Cord
Branch Circuit
Length
Required (Amps)
in ft. (m)
20
20 (6.1)
15
20 (6.1)
15
20 (6.1)

Control Panels

motor before connecting controls or power supply.
Adhere to local electrical codes governing pump and
control installations.
A control panel is not included with the pump.
Install simplex or duplex control panel (purchase
separately) for proper pump operation. A full range of
controls and switches is listed in our catalog.
If a Hydromatic control panel is not used, install a
control panel with circuit breaker or fused disconnect
as required by local code. Use magnetic starters with
ambient compensated overload protection. Three phase
units require three line protection; single phase units
require only one line protection. Inadequate protection
voids the warranty.
Control Panel Overload Adjustment – Three
Phase
NOTE: See your con trol panel in stallation and operating
instructions before adjusting overload setting.
Set the overload protective device to the nameplate full
load current.
Size the overload protective device so that the trip
current is 115% of the nameplate full load current.
Z2
Minimum
Discharge
Water Level
Adapter
in inches (mm)
Size
 22-1/2 (572)
1-1/4 NPT
19-1/2 (496)
1-1/4 NPT
19-1/2 (496)
1-1/4 NPT
Risk of electric shock. Ground pump and
4
Max Temp.
Rating (°F)
Intermittent
122
122
122

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hydromatic hpgr200-d3Hydromatic hpgr200-d4

Table of Contents