NOTES:
① When the fan speed of IDU is adjusted to auto, the IDU will automatically
change the fan speed according to the indoor ambient temperature to make
the indoor ambient temperature more stable and comfortable.
② Only when the control mode is set as auto can the auto fan speed be valid.
③ Fan and control mode of ERV are bound.

8.5 Setting of Control Modes

Under on status, the unit will change in the sequence of auto→linkage→operation circularly
after pressing "
" button.
Auto control mode: when turning on the unit, ERV+DX Coil will be started up or
stay at the standby status according to the air quality detected by the air box; when
turning off the unit, the unit will stop operation.
Linkage control mode: when turning on the unit, ERV+DX Coil will be started up
or stay at the standby status according to the on/off of the indoor unit of linked VRF
unit. when turning off the unit, the unit stops operation.
Operation control mode: when turning on the unit, ERV+DX Coil operates
continuously; when turning off the unit, the unit stops operation.
NOTES:
① Under HBS linkage mode, "linkage" can be started up only when the
ERV+DX Coil and the general air conditioning indoor unit under the same
Wired Controller XE70-33/H