Nec Power-Limited Wiring Requirements - Altronix Maximal3FV Installation Manual

Access power controllers with power supplies
Hide thumbs Also See for Maximal3FV:
Table of Contents

Advertisement

Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited
circuit wiring must remain at least 0.25" away from any non power-limited circuit wiring. Furthermore, all
power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through differ-
ent conduits. One such example of this is shown below. Your specific application may require different conduit
knockouts to be used. Any conduit knockouts may be used. For power-limited applications use of conduit is
optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or
equivalent substitute). Optional battery enclosure must be mounted adjacent to the power supply.
For Canadian installations use shielded wiring for all connections.
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 4a).
Fig. 4
Input
220VAC, 50/60Hz
(non power-limited)
Fig. 4a
Incorrect Wire
Handling
Insulation
Solid Copper
Conductors
- 10 -

NEC Power-Limited Wiring Requirements:

Battery
Connections
(non power-limited)
Correct Wire
Handling
External
Jacketed
Shield
Wire
Pull back
external jacketed
shield approx. 1/2".
Supervisory Connections
(power-limited)
Maximal3FV / Maximal5FV / Maximal7FV Access Power Controllers (Fused)
Optional
Battery Enclosure
(non
power-limited)
Supervisory
Connections
(power-limited)
Supervisory
Connections
(power-limited)
ACM8 outputs
(non power-
limited)
Supervisory
Connections
(power-limited)