INSTALLING THE GAS COOKER

Gas connection point to regulator
168
Model: WFE912SB
Electrical connection cable
Gas pressures
The following table shows the supply and operating
pressures for various gases.
GAS TYPE
Supply pressure at inlet
to appliance regulator
(if fitted)
Operating pressure at
appliance test point
*If the regulator is placed upstream of the cooker inlet, as is normal
for cookers operating on LPG, then the supply pressure and
operating pressure are the same.
The following table shows the injector sizes for
each burner.
INJECTOR ORIFICE
Low heat burner
Medium heat burner
High heat burner
Intense heat wok
burner
Checking piping size
To work out a suitable pipe size for connection use the
information in this table.
GAS TYPE
WFE912
For information and requirements about construction
and capacity of consumer piping refer to AS5601 series
of standards.
28
INSTALLING THE GAS COOKER
Electrical cable
entry point
95
NATURAL
UNIVERSAL
GAS
LPG
1.13 (kPa)
2.75*
Minimum
(kPa)
1.00 (kPa)
2.6 (kPa)
NATURAL
UNIVERSAL
GAS
LPG
1.00mm
0.55mm
1.35mm
0.70mm
1.60mm
0.90mm
1.75mm
1.00mm
NATURAL
UNIVERSAL
GAS
LPG
49.6 MJ/h
40.9 MJ/h
Gas connection
Read these points before connecting to the gas supply:
The appliance is preset for natural gas use, if LPG is
to be used see Conversion to LPG section.
Gas installation must be made in accordance with AS/
NZS5601.1, the local gas fitting regulations, municipal
codes and other statutory regulations.
The gas connection point is a ½" BSP external thread
located at the rear of the appliance as shown.
The regulator is to be fitted to the manifold inlet at
the rear of the appliance and the connectionis sealed
using a tape or jointing compound suitable for gas
connections. The consumer piping is then connected to
the inlet of the regulator, either
1. directly, or
2. using a hose assembly and in accordance
with Clause 6.10.1.9 of AS 560101 (High level
connection) together with the supplied elbow.
The elbow is fitted to the inlet of the regulator
and oriented to allow the hose to hang
downward. The connection thread between the
regulator and elbow is sealed using a tape or
jointing compound suitable for gas connections.