Override Button; Setpoint Type; Discharge Air Sensor; Optional Sensor - Honeywell S7751A Product Data

Excel 10 hand held tool
Table of Contents

Advertisement

Use the Up/Down Arrow keys to select the type of FAN required for the configuration and then press the Enter key. The
operator has to press the Prev Menu key to get back to the APPLICATION TYPE Main Menu.

Override Button

Use the Up/Down Arrow keys to select the Override Button sub-menu item and then press the Enter key to display the two
selections available.
O V E R R I D E B U T T O N
Y e s
N o
Select whether or not the OVERRIDE BUTTON is connected for the configuration by using the Up/Down Arrow keys and
then pressing the Enter key. The operator has to press the Prev Menu key to get back to the APPLICATION TYPE Main
Menu.

Setpoint Type

Use the Up/Down Arrow keys to select the Setpoint Type sub-menu item from the APPLICATION TYPE Main Menu and
then press the Enter key to display the three selections available.
S E T P O I N T T Y P E
N o n e O n W a l l
Absolute
Relative
SETPOINT TYPE allows the operator to set the temperature control loop type in use by this configuration. None On Wall
displays when (nv_config.flow_cnt_mode) is Share_wall_module or Dual_duct_slave (View only, not configurable). Absolute
allows the operator to use the temperature control algorithm. Relative allows the operator to turn the temperature control off
and the flow setpoint is supplied from a different node. Select the SETPOINT by using the Up/Down Arrow keys and then
pressing the Enter key. The operator has to press the Prev Menu key to get back to the APPLICATION TYPE Main Menu.

Discharge Air Sensor

Use the Up/Down Arrow keys to select the Discharge Air Sensor sub-menu item from the APPLICATION TYPE Main Menu
and then press the Enter key to display the two selections available.
D I S C H A R G E A I R S E N S O R
Y e s
N o
Select whether or not the DISCHARGE AIR SENSOR is connected by using the Up/Down Arrow keys and then pressing the
Enter key. The operator has to press the Prev Menu key to get back to the APPLICATION TYPE Main Menu.

Optional Sensor

Use the Up/Down Arrow keys to select the Optional Sensor sub-menu item from the APPLICATION TYPE Main Menu to
choose whether or not an occupancy or window sensor is connected and then press the Enter key to display the two
selections.
Page 29
EXCEL 10 HAND HELD TOOL
74-2566

Advertisement

Table of Contents
loading

Table of Contents