Temp Setpoints
Select the Temp Setpoints menu item using the Up/Down Arrow keys and then press the Enter key. Under the Temp
Setpoints heading the operator is able to display/modify the current value of the points listed in the Temp Setpoints table
shown below, see Table 5.
This table shows that an operator must be logged on as a level 2 operator in order to modify the setpoint values. If the
operator has logged onto a level less than level 2, then the screen displays only the data and engineering units for that point
as shown in the previous screen view for the Room Temp .
HHT Point Name
Occupied Cool
Standby Cool
Unoccupied Cool
Occupied Heat
Heat/Cool Deadband
Standby Heat
Unoccupied Heat
Select the Occupied Cool setpoint menu item using the Up/Down Arrow keys and then press the Enter key. If the operator
has logged on as a level 2 operator, the following screen displays the setpoint value and engineering unit for the Occupied
Cool setpoint and prompts the operator for a new setpoint value.
Occupied Cool
Setpoint is 72.0
D e g F
New setpoint ?
The operator can either press the Prev Menu key to go back to the previous menu and use the Up/Down Arrow keys to
display a different setpoint or can enter a new setpoint value, for this point, and then press the Enter key to accept the new
value. When the Enter key is pressed, the HHT limits the ranges to the following:
 Temperature setpoints:
50 through 90 ° F (10 through 32.2 ° C)
 Heat/Cool Deadband:
0 through 10 ° F (-17.8 through -12.2 ° C)
The HHT enforces the following relationships (when the Enter key is pressed):
 Setpoint Value range of 40 to 90 ° F (4 to 32 ° C)
 Heating Unoccupied < Heating Standby
 Heating Standby < Heating Occupied
 Heating Occupied < Cooling Occupied
 Cooling Occupied < Cooling Standby
 Cooling Standby < Cooling Unoccupied
Excel 10 defaults:
 Occupied Cool:
72 ° F (22.2 ° C)
 Standby Cool:
75 ° F (23.9 ° C)
 Unoccupied Cool:
85 ° F (29.4 ° C)
 Occupied Heat:
70 ° F (21 ° C)
 Heat/Cool Deadband:
2 ° F (-16.7 ° C)
Table 5. Temp Setpoints.
R/W Read Write or R/O Read Only
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Write Access Level
2
2
2
2
2
2
2
Page 13
EXCEL 10 HAND HELD TOOL
Input/ Output
Input
Input
Input
Input
Input
Input
Input
74-2566