HHT Point Name
Manual Occupancy
Command Mode
Manual Reheat Posit.
Manual Damper/Flow
Select the Manual Occupancy menu item from the list of points under the Commandable Points menu and then press the
Enter key to display the state. The following screen displays the current Manual Occupancy state.
Manual Occupancy
Current: Occupied
New State:
<choices>
To enter a new state, the operator will scroll through the choices by using the arrow keys and select the state by pressing the
Enter key. Press the Refresh key to read the point data and update the display.
The operator can press the Prev Menu key to go back to the previous menu to display another Commandable Point .
Select the Command Mode from the list of points under the Commandable Points menu and press the Enter key to display
the state. The following screen displays the current Command Mode (Auto).
C o m m a n d M o d e
Current: Auto
New State:
<choices>
To enter a new state, the operator scrolls through the choices by using the Up/Down Arrow keys and then selects a state by
pressing the Enter key. Press the Refresh key to read the point data and update the display.
The operator can press the Prev Menu key to go back to the previous menu to display another Commandable Point .
Select the Manual Reheat Posit. from the list of points under the Commandable Points menu and then press the Enter key
to display the state. The following screen displays the current Manual Reheat Posit. ( Auto ).
Manual Reheat Posit.
Current State: Auto
New State:
<choices>
To enter a new state, the operator scrolls through the choices (Auto or Manual) by using the Up/Down Arrow keys and then
selects a state by pressing the Enter key. If Manual is selected, the second line of the screen will change to Manual
Percent? . The operator can enter a new value (for example 50.0) on the third line of the display and then press the Enter key.
The following screen shows the new value.
Manual Reheat Posit.
Manual Percent?
New Value: 50.0
Table 7. Commandable Points.
R/W Read Write or R/O Read Only
R/W
R/W
R/W
R/W
Write Access Level
3
3
3
3
Page 15
EXCEL 10 HAND HELD TOOL
Input/ Output
Input
Input
Input
Input
74-2566