A I R F L O W S E T P O I N T S
Maximum <cfm>
Minimum <cfm>
Reheat <cfm>
The display shows the current AIR FLOW SETPOINTS and allows the operator to enter new values for each field using the
Up/Down Arrow keys/keyboard and then press the Enter key. The HHT limits the ranges from 0 through 10,000 CFM for all
of the AIR FLOW SETPOINTS . The default setpoints are.
Maximum
Minimum
Reheat
NOTES: If the operator enters Maximum at zero and Minimum at zero, a pressure dependent application, the operator must
enter a value that represents the percentage (a range of 0 through 100 percent) of the full damper position for reheat.
Air flow Curve Table
From the PARAMETERS Main Menu, the operator can select the Air flow Curve Table menu item and then press the Enter
key. The HHT displays the SELECT PICKUP SENSOR screen containing nine sub-menus.
S E L E C T P I C K U P S E N S O R
Carrier 35R Probe
Honeywell C705 Sens
Titus 6,8,10,12,14,16
Titus Pickup 4.5 in.
Titus Pickup 7.9 in.
Trane 16 inch
Trane 5 inch
Trane 6 inch
Trane 8,10,12,14 in.
After choosing the PICKUP SENSOR and then pressing Enter , the next display prompts the operator to SELECT DUCT
DIAMETER in inches from the following list of 14 values (4, 5, 6, 8, 10, 12, 14, 16, 18, 20 ,22, 24, 26, and 30).
1500 CFM
700 CFM
1000 CFM
Page 31
EXCEL 10 HAND HELD TOOL
74-2566