Honeywell S7751A Product Data page 16

Excel 10 hand held tool
Table of Contents

Advertisement

EXCEL 10 HAND HELD TOOL
As soon as the Enter key is pressed, the screen displays the current state as manual and the new value (as a percentage) as
shown below.
Manual Reheat Posit.
Current State: Manual
50.0 %
To command the Manual Reheat Posit. point to the Auto state, the operator presses the Prev Menu key to go back to the
previous menu, then selects the Manual Reheat Posit. from the list of points and presses the Enter key to display the state.
The operator scrolls through the choices ( Auto or Manual ) and chooses Auto by using the Up/Down Arrow keys and then
presses the Enter key to select the Auto state. Press the Refresh key to read the point data and update the display to verify
that the Manual Reheat Posit. point is in the Auto state.
The operator can press the Prev Menu key to go back to the previous menu to display another Commandable Point .
Select the Manual Damper/Flow from the list of points under the Commandable Points menu and then press the Enter key
to display the state. The following screen displays the current Manual Damper/Flow ( Auto ).
Manual Damper/Flow
Current State: Auto
New State:
<choices>
To enter a new state, the operator scrolls through the choices by using the Up/Down Arrow keys and then selects the state
by pressing the Enter key. If Manual Damper was selected, then the following screen displays and prompts the operator to
enter a new damper position value. In the example below the current position of the damper is 67.0 % and the operator
commands the damper to a new position of 25.0 %.
Manual Damper
67.0 %
New Position:
25.0
If Manual Flow was selected, then the following screen displays and prompts the operator to enter a New Flow value. In the
example below the current flow value is 934.0 CFM and the operator commands the damper to a new value of 800.0 CFM.
Manual Flow
9 3 4 . 0 C F M
New Flow:
800.0
To put the Manual Damper/Flow point into the Auto mode (normal program control), the operator can press the Prev Menu
key to go back to the previous menu, select the Manual Damper/Flow from the list of points under the Commandable
Points menu, and then press the Enter key to display the state. The following screen displays the current Manual
Damper/Flow ( Man Flow ).
Manual Damper/Flow
Current State:Man Flow
New State:
<choices>
95-2566
16