CHAPTER 3: USER INTERFACE
DGT DISTRIBUTED GENERATION TRIP CONTROL SYSTEM – INSTRUCTION MANUAL
DGT-D Transceiver layout
TERMINATIONS
LED PANEL
Power, Link, Inputs/Outputs
(configurations vary)
RF OUTPUT
Antenna Connector (TNC)
902 to 928 MHz (FHSS)
Power (PWR) LED illuminates when power is applied to the radio.
The Link LED illuminates when the DGT-D transceiver has established a connection
with a DGT-R transceiver.
The Service (SERV) LED flashes whenever a transceiver alarm condition is detected or
if any of the configured outputs are in a failsafe state.
The input LED (IN) is illuminated whenever the auxiliary contact from the breaker is
energized.
The output LED (OUT-1) illuminates whenever the associated output is energized.
OUT-1 reflects the state of the trip input on the DGT-U within the network. If the
output is in a failsafe state, the LED flashes a unique pattern to indicate this state. If
the output is configured and mapped to two inputs (when taking Trip signals from a
Recloser) and data is only being received from one of the two inputs, the LED flashes a
unique pattern to indicate this state.
The output LED (OUT-2) is reserved for future use.
PRIMARY POWER
+
+
1 to 4
24 VDC POWER OUTPUT
5 to 8
PWR
LINK
SERV
IN
OUT-1
OUT-2
CONFIGURATION
DCE Console/Terminal
19,200 bps/8N1 (Default)
CONFIG
No Handshaking
RS/EIA-232
ANT
TERMINATIONS
9 to 12
13 to 16
TRANSCEIVER LAYOUTS
13.8 Vdc @ 350 mA
(6 to 30 Vdc)
Negative Ground
1 + / 2
-
24.0 Vdc @ 40 mA
Isolated from Ground
Pins 3 (+) and 4 (-)
3–21