TRANSCEIVER LAYOUTS
3–20
within the network. If the output is in a failsafe state, the LED shall flash a unique
pattern to indicate this state.
•
The output LED (OUT-2) illuminates whenever the associated output is energized.
OUT-2 will reflect the state of the status input on the DGT-D radio configured for Slot 2
within the network. If the output is in a failsafe state, the LED shall flash a unique
pattern to indicate this state.
•
The output LED (OUT-3) illuminates whenever the associated output is energized.
OUT-3 will reflect the state of the status input on the DGT-D radio configured for Slot 3
within the network. If the output is in a failsafe state, the LED shall flash a unique
pattern to indicate this state.
•
The output LED (OUT-4) illuminates whenever the associated output is energized.
OUT-4 will reflect the state of the status input on the DGT-D radio configured for Slot 4
within the network. If the output is in a failsafe state, the LED shall flash a unique
pattern to indicate this state.
•
The output LED (OUT-5) illuminates whenever the associated output is energized.
OUT-5 will reflect the state of the status input on the DGT-D radio configured for Slot 5
within the network. If the output is in a failsafe state, the LED shall flash a unique
pattern to indicate this state.
•
The output LED (OUT-6) illuminates whenever the associated output is energized.
OUT-6 will reflect the state of the status input on the DGT-D radio configured for Slot 6
within the network. If the output is in a failsafe state, the LED shall flash a unique
pattern to indicate this state
•
The output LED (OUT-7) illuminates whenever the associated output is energized.
OUT-7 will reflect the state of the status input on the DGT-D radio configured for Slot 7
within the network. If the output is in a failsafe state, the LED shall flash a unique
pattern to indicate this state.
DGT-R Transceiver layout
REPROGRAMMING PORT
◆
For reprogramming firmware
◆
10-Base-T
◆ IP/Ethernet Port
◆
IP Address: 192.168.0.1
•
Power (PWR) LED illuminates when power is applied to the radio. When the
transceiver is experiencing a fault condition, the Power LED flashes once per second.
•
The COM1 LED blinks with serial traffic activity to and from the COM1 serial interface.
•
The LINK LED illuminates during normal operation and blinks when there is over-the-
air traffic activity.
DGT DISTRIBUTED GENERATION TRIP CONTROL SYSTEM – INSTRUCTION MANUAL
COM1
◆
DCE (Console/Terminal only)
◆ 19,200 bps/8N1
◆
No Handshaking
◆
RS/EIA-232
RESERVED
◆
This port reserved for future expansion
CHAPTER 3: USER INTERFACE
ANTENNA
◆
50 Ohm
TNC
◆
+30 dBm/1W Out (Max.)
◆
-30 dBm Input (Max.)
PRIMARY POWER
◆ 6 to 30 Vdc (800 ma @ 13.8 Vdc)
◆
Negative Ground