Completing Commissioning - Condair MD Series Commissioning Manual

Advertisement

Bleeding 2/3
Please bleed now the
the heat exchanger!
It is described in
more detail in the
HumiLife KWL manual
.
You have 10min time.
10. Confirm message.
13. Whether the pump is properly bled can be determined by the flashing code of the LED on the pump:
Pump in normal operation:
Bleeding necessary:
If the pump indicates the error "bleeding necessary", you can remove air bubbles trapped in the pump by repeatedly
setting the rotary switch to level 7, followed by level 0.
14. If there is humidity demand, set "Operating Mode" to "Humidify" under "Menu > User Settings > Operation". Turn on
KWL.
System Status
9

Completing commissioning

Control State
Setpoint Hum.
1. Under "Menu > Information > System Status > W.Temp Actual" you can follow the warm up of the water in the water
Actual Humidity
circuit between the hydraulic unit and the humidifier unit.
Demand
Air Temp Actual
System Status
Flow Setpoint
Control State
Flow Actual
Setpoint Hum.
Flow Output
Actual Humidity
W.Temp Setpoint
Demand
W.Temp Actual
Air Temp Actual
W.Temp Out CH1
Flow Setpoint
W.Temp Out CH2
Flow Actual
Water Condu.
100uS/cm
Flow Output
If the water does not warm up, this could be for the following reasons:
Condu. Limit
500uS/cm
W.Temp Setpoint
Lekage Fins
a) The integrated pump of the unit variants MD-HW-H and MD-WW-H can not supply enough water. Gradually raise
W.Temp Actual
the rotary switch on the integrated pump.
Minimal Speed
W.Temp Out CH1
b) The heating/hot water circuit was not correctly bled. Repeat bleeding.
W.Temp Out CH2
2. After a short delay, the color of the drop icon in the upper right corner of the display indicates the operating status:
Water Condu.
100uS/cm
Condu. Limit
500uS/cm
Lekage Fins
Unit commissioned without fault, unit works correctly.
green
Minimal Speed
or
There is a failure/error. Please refer to the information on troubleshooting in the operation manual.
yellow
red
Bleeding 3/3
The system stops the
bleeding. Should still be
air in the system, the
bleeding can be repeated
at any time
11. Confirm message.
LED on
LED 200 ms on, 200 ms off 200 ms on
Humidify
45.0%rH
39.0%rH
75.0%
22.0°C
1.5l/min
Humidify
1.4l/min
45.0%rH
60%
39.0%rH
35.0°C
75.0%
33.0°C
22.0°C
20.0%
1.5l/min
100.0%
1.4l/min
60%
35.0°C
0.0V
33.0°C
0%
20.0%
100.0%
0.0V
0%
.
12. Set the rotary switch of the circu-
lation pump to level 3.
9