1
Checks before first commissioning
1. Check ERV filters: For hygienic operation of the Condair MD, use at least filter of class G4 (recommendation:
F7). Install new air filters before operating the Condair MD for the first time.
2. Check electrical installations (see installation and commissioning manual).
3. Carry out a visual inspection of the hydraulic unit (see installation and commissioning manual).
4. Obtain inlet water values (water hardness, pH value) for the installation site from the local water works.
2
Installation of the humidifier insert
1. Remove cover of the humidifier unit.
2. Clean the inside of the humidifier housing and the cover with a lint-free cloth and mild detergent/disinfectant. To clean,
remove bottom plate (c) and then reinstall.
3. Remove blanking plugs.
4. Push the two pieces of hose "a" (from the installation kit) as far as they will go into the plug-in couplings on the black
water distributors of the humidifier insert (b).
5. Place the humidifier insert on the bottom plate (c) in the humidifier housing, push it into the humidifier housing as far
as it will go and press it into the end position. Important: Make sure that the arrows on the water connections of the
elements of the humidifier insert correspond to the direction of the water flow.
6. Replace cover of the humidifier unit and lock it.
3
Commissioning of the water treatment device
Put the optional water treatment device (decarboniser or reverse osmosis system Condair RO-HS) into operation according
to the separate manual of the respective product.
2
3
c
4
a
5
Flussrichtung
Wasser
2
b
6
1