Condair Plc, except to the extent required for installation or maintenance of recipient's equipment. Liability Notice Condair Plc does not accept any liability due to incorrect installation or operation of the equipment or due to the use of parts/components/equipment that are not authorized by Condair Plc.
Contents Introduction Notes on the addendum manual For your safety System Overview / Principle of Operation Installation work Installing the UV lamp(s) Installing the power distribution box Connecting the 3 core connecting cable to the terminals in the control unit Test function / Reset UV lamp service interval counter Test function of the submerged UV system Reset UV bulb service interval counter...
Introduction Notes on the addendum manual This manual is an addendum for the installation of the optional submerged UV system for the Condair ME Control and must be read in conjunction with the installation manual and operation manual for Condair ME Control.
It is assumed that all persons working with the submerged UV system and the Condair ME Control are familiar and comply with the appropriate local regulations on work safety and the prevention of accidents.
Page 6
Prohibited modifications to the unit No modifications must be undertaken on the submerged UV system without the express written consent of the manufacturer. For the replacement of defective components use exclusively original accessories and spare parts available from your Condair representative. For your safety...
When the water level in the tank reaches the lower operating level the lamps switch on. UV light is ef- fective in killing bacteria in water systems. However the Condair ME system should always be supplied with a clean water supply (refer to installation manual and operation manual).
The installation procedure is dependant on whether the submerged UV system is retrofitted on an exist- ing Condair ME Control system or on a new Condair ME Control system. Note: Steps 1 to 4 must be performed only, if the submerged UV system is retrofitted on an existing Con- dair ME Control system.
Page 9
6. Carefully push the UV lamp assembly into the circular clips of the two corresponding brackets. Re- peat for all UV lamps. Fig. 3: Attaching mounting brackets 7. Affix the supplied yellow UV light caution label to the tank in a clearly visible position. Fig.
Note: The cable feed through must be done by the customer and must be equipped with cable glands. 4. Secure 3 core connecting cable with cable ties at suitable intervals along the cable run to the Condair ME control unit.
Connecting the 3 core connecting cable to the terminals in the control unit 1. Isolate power supply to the Condair ME control unit. 2. Remove the front cover of the control unit. CAUTION! Electronic components are very sensitive to electrostatic discharge. Before proceeding with the next step, appropriate measures (ESDprotection) must be taken to prevent damage to electronic...
Test function / Reset UV lamp service interval counter Test function of the submerged UV system 1. Restart system in accordance with restart section in the Condair ME Control operation manual. 2. Wait until tank is filled to operating level.
Although the lamp may still be emitting UV light, the performance may have deteriorated to less effec- tive levels. To avoid risk of leaks at the sealing grommets from incorrect assembly, Condair Plc only offer complete lamp assemblies. These include the cabling and plug for quick and easy replacement.