SHORT FORM -
COMMISSIONING MANUAL
Condair HumiLife – The efficient ERV-solution
Condair MD
MD-EL-H
MD-FB-H
MD-HW-H
MD-WW-H
Humidification and Evaporative Cooling

Advertisement

loading

Summary of Contents for Condair MD Series

  • Page 1 SHORT FORM - COMMISSIONING MANUAL Condair HumiLife – The efficient ERV-solution Condair MD MD-EL-H MD-FB-H MD-HW-H MD-WW-H Humidification and Evaporative Cooling...
  • Page 2 Checks before first commissioning 1. Check ERV filters: For hygienic operation of the Condair MD, use at least filter of class G4 (recommendation: F7). Install new air filters before operating the Condair MD for the first time. 2. Check electrical installations (see installation and commissioning manual).
  • Page 3 Configuration of the control software 1. Put ERV into operation. 2. Plug in mains cable and switch on hydraulic unit. 3. Control software starts with the installation routine. Note: The installation routine is only started automatically when the hydraulic unit is switched on for the first time. If the humidifier has already been switched on, the installation routine must be started manually under "Menu>...
  • Page 4 Code: MD-EL-H FB + 1HE Condair MD-FB-H with additional el. heating element Condair MD-HW-H Condair MD-WW-H Engineered in Switzerland, Made in Germany If the unit variant does not match the specification on the type plate, please contact the Condair Support.
  • Page 5 3. Switch on the hydraulic unit of the Condair MD. 4. Switch the ERV to the lowest fan speed. 5. Slowly turn the "Sensitivity" trimmer clockwise towards maximum until the yellow LED lights up. Turn the trimmer a little over the switching point.
  • Page 6 WW-H: Set the rotary switch of the under "Menu > User Settings > circulation pump to level 4. Operation". Humidity Level Condair MD 40%rH 45%rH High 80%rH 4. Select humidification level High (3 5. Under "Menu> User Settings> Hu- drops) in the home screen.
  • Page 7 Manual bleeding variant MD-FB-H 1. Switch off hydraulic unit. 2. Make sure that the heating water circuit is in operation. 3. Place absorbent rag under the armored hose in the hydraulic unit (see Fig. 4. Unscrew the valve drive of the zone valve. 5.
  • Page 8 Manual bleeding variants MD-HW-H, MD-WW-H 1. Switch off ERV, switch on hydraulic unit and set "Operating Mode" to "Standby" under "Menu > User Settings > Opera- tion". 2. Open shut-off valves in the supply and return line. 3. Place absorbent rag under the armored hose in the hydraulic unit (see Fig.
  • Page 9: Completing Commissioning

    Bleeding 2/3 Bleeding 3/3 Please bleed now the The system stops the the heat exchanger! bleeding. Should still be It is described in air in the system, the more detail in the bleeding can be repeated HumiLife KWL manual at any time You have 10min time.
  • Page 10 Guarantee of hygienic operation After initial commissioning, the Condair MD must not be switched off and must be operated either in the operating mode "Humidity" (humidity required) or "Standby" (no humidity required). This is the only way to ensure that the water system will flush periodically and that there is no microbial contamination of the system by stagnant water.
  • Page 12 All information in this short form commissioning manual is for general information only and is intended for trained personnel who have read and understood the installation and commissioning manual for the Condair MD. The information in the installation and commissioning manual for the Condair MD must be adhered to.