4
Configuration of the control software
1. Put ERV into operation.
2. Plug in mains cable and switch on hydraulic unit.
3. Control software starts with the installation routine.
Note: The installation routine is only started automatically when the hydraulic unit is switched on for the first time. If the
humidifier has already been switched on, the installation routine must be started manually under "Menu> User Settings>
Installation> Install.Seq."
HumiLife
Start screen
Pumping head
0.5m
Enter pumping head and confirm.
Pumping head= Vertical distance bet-
ween upper edge of hydraulic unit and
lower edge of humidifier unit.
WT Cartridge
XL
XXL
Display appears only when "Water
Supply" is set to "WT option".
Set Cartridge size of water treatment
device and confirm.
Language
English
Deutsch
Français
Italiano
Select language and confirm.
Control Mode
On / Off
Ext Cntrl
Ext Air
Ext. Setpnt
Inlet Air
Inl+Ext.Hyg
Define control mode and confirm.
Standard DE/AT: "Inlet Air"
Standard CH: "Ext Air"
For more information on control modes
see installation and commissioning
manual.
Water Hardness
20.0dH
Display appears only when "Water
Supply" is set to "Tap water" or "WT
option".
Water hardness in °dH of the instal-
lation site and confirm (Conversion:
1 °fH = 0.56 °dH).
Installation
This procedure guides you
through the input of
required values for the
HumiLife ERV to operate
properly
Confirm start of installation routine.
Water Supply
Tap water
WT option
Rev. osm.
Set type of water supply and confirm.
Standard: "Tap Water"
For more information on water supply
types, see the installation and com-
missioning manual.
Water pH
7.50
Display appears only when "Water
Supply" is set to "Tap water" or "WT
option"
Enter the pH value of the water at the
installation site and confirm.
3