IMPORTANT! Read and save these instructions.
This manual to be left with the equipment.
PLANNING AND INSTALLATION
INSTRUCTIONS
Condair HumiLife - The flexible room solution
Condair MN
Humidification and Evaporative Cooling

Advertisement

Table of Contents
loading

Summary of Contents for Condair MN Series

  • Page 1 IMPORTANT! Read and save these instructions. This manual to be left with the equipment. PLANNING AND INSTALLATION INSTRUCTIONS Condair HumiLife - The flexible room solution Condair MN Humidification and Evaporative Cooling...
  • Page 2 Condair Ltd., except to the extent required for installation or maintenance of recipient's equipment. Liability Notice Condair Ltd. does not accept any liability due to incorrect installation or operation of the equipment or due to the use of parts/components/equipment that are not authorized by Condair Ltd.
  • Page 3: Table Of Contents

    Information on positioning of the components of the optional reverse osmosis system Condair RO-HB Positioning the humidifier units Water supply requirements 4.8.1 Water supply requirements (without RO system) 4.8.2 Water supply requirements for the reverse osmosis system Condair RO-HB Water outlet requirements 4.10 Power supply requirements 4.11 LAN connection requirements 4.12 Information on servicing the Condair MN 4.13...
  • Page 4 Drill wall duct(s) 5.6.2 Laying cable ducts Installing the central unit and water filter(s) in the housing Installing the components of the optional reverse osmosis system Condair RO-HB Setting up water inlet and outlet 5.9.1 Information on water installation 5.9.2 Water installation overview 5.9.3...
  • Page 5: Introduction

    First things first! Thank you for choosing the Condair MN. The Condair MN has been built using state-of-the-art technology and in accordance with the latest safety regulations. However, improper installation and use of the Condair MN may put users and/or third parties at risk and may also cause damage to material assets.
  • Page 6 Keep this documentation in a safe place for further use. If these instructions are lost or if you are unsure whether this documentation is still up to date, please contact your Condair representative. Language versions This documentation is available in various languages. For more information, please contact your Condair representative. Introduction...
  • Page 7: For Your Safety

    Furthermore, for safety and warranty reasons, interventions may only be undertaken by specialist personnel authorised by Condair. It is assumed that all persons entrusted to work on the Condair MN are familiar with and abide by the regulations on occupational health and safety and accident prevention.
  • Page 8 DANGER! Risk of electrocution The Condair MN's central unit runs on mains power. If the central unit is open, live parts may be touched. Touching live parts may cause severe injury or death. That is why the central unit must be switched off and disconnected from the mains power supply (remove the plug from the socket) before the central unit is opened.
  • Page 9 Preventing hazardous operating conditions If it is suspected that safe operation is no longer possible, the Condair MN should immediately be shut down and secured against accidental power-up. Then, contact the Condair representative. This can be the case under the following circumstances: –...
  • Page 10: Product Overview

    The identification of the product is found on the specification label on the right side of the central unit: Production Type designation Serial number (7 digits) Month/Year Condair Ltd., 2740 Fenton Road, Ottawa, Ontario K1T3T7 Supply voltage Type: Condair MN Serial-No: XXXXXXX 02.20 Voltage: 115 1~ / 60Hz Power: max.
  • Page 11: System Overviews

    Hoses LAN gateway Mains power sockets for central unit and LAN gateway (provided on site) LAN connection (provided on site) LAN cable (provided on site) Fig. 2: Overview of Condair MN system with central drainage of spray circuit Product overview...
  • Page 12 Mains power sockets for central unit and LAN gateway (provided on site) LAN connection (provided on site) LAN cable (provided on site) CAN bus cable Water hoses Humidifier units Fig. 3: Overview Condair MN system with central drainage of spray circuit and reverse osmosis system Condair RO-HB Product overview...
  • Page 13 Drainage module (installed externally) LAN gateway Mains power sockets for central unit and LAN gateway (provided on site) LAN connection (provided on site) LAN cable (provided on site) Fig. 4: Overview of Condair MN system with peripheral drainage of spray circuit Product overview...
  • Page 14 LAN connection (provided on site) LAN cable (provided on site) CAN bus cable Water hoses Humidifier units Drainage module (mounted externally) Fig. 5: Overview of Condair MN system with peripheral drainage of spray circuit and reverse osmo- sis system Condair RO-HB Product overview...
  • Page 15: System Description

    Note: The booster modules are available in a version for single systems (to feed a single Condair MN system) and a version for multiple systems (to feed up to 3 Condair MN systems). In the case of mul- tiple systems, the individual Condair MN systems can only be equipped with one water filter and one booster module is required for each Condair MN system.
  • Page 16 Installing the humidifier units The humidifier units are flush-mounted onto a ceiling or wall as standard. In concrete ceilings/walls in new buildings, flush-mounting boxes must be placed in the relevant positions and connected using guide pipes (0.98" (25 mm) in diameter for the insertion of hoses and CAN bus cables). When install- ing humidifier units in suspended ceilings in new or existing buildings, holes ø2.95"...
  • Page 17 Guide pipe Guide pipe ø0.98" (ø25 mm) ø0.98" (ø25 mm) Guide pipe Guide pipe ø0.98" (ø25 mm) ø0.98" (ø25 mm) Drill hole Drill hole ø2.95" (ø75 mm) ø2.95" (ø75 mm) in ceiling in ceiling Catch springs Installation on both sides ring Installation ring...
  • Page 18 – Open drain funnel with trap connected to the building's wastewater pipe. Hygiene functions In order to comply with the guidelines set out in VDI 6022, sheet 6, the Condair MN has the following hygiene functions as standard: – Periodic system flushing –...
  • Page 19: Spray Circuit Design

    Spray circuit design Room 2 Room 3 Room 2 Room 3 Room 4 Room 1 Zone 5 Zone 3 Zone 2 Zone 4 Room 1 Room 4 Bathroom Kitchen Kitchen Bathroom Zone 1 Zone 6 CU: Central unit 1x CAN bus cable HU: Humidifier unit 1x hose DM: Drainage module (peripheral drainage)
  • Page 20: Options

    Options Second water filter in housing Second water filter to prolong the interval between filter replacements. Water filter without housing Water filter without housing for placing on the ground. Serves as an alternative to the first and/ or second water filter if there is no room to attach the water filter in the housing at the installation site.
  • Page 21 Reverse osmosis system RO-HB Reverse osmosis system RO-HB consisting of the reverse osmosis unit Condair RO-H and the 12 l flow tank for feeding the central unit with RO water. Note: A booster module is additionally required to operate the Condair MN system with the RO-HB reverse osmosis system.
  • Page 22: Planning A Condair Mn System

    Planning a Condair MN system Note on the water supply to the Condair MN The Condair MN can be operated with raw water (drinking water) or with RO water from the reverse osmosis system Condair RO-HB. For larger systems or systems with a high number of operating days and/or with a high number of op- erating hours per day, the use of the reverse osmosis system RO-HB for the treatment of the supply water must be considered.
  • Page 23: Calculating Cable And Hose Lengths

    262 ft (80 m) 58.0 psig (400 kPa) up to 328 ft (100 m) 65.3 psig (450 kP) up to 361 ft (110 m) 72.5 psig (500 kPa) up to 394 ft (120 m) Planning a Condair MN system...
  • Page 24: Information On Positioning The Central Unit And Water Filter(S)

    2.2" (55) 0.4" (10) 0.8" (20) Ensure sufficient space (min. 11.8" (min. 300 mm)) 6.1" (156) to position the drain funnel with trap Fig. 10: Central unit and water filter dimensions (dimensions in inch (mm)) Planning a Condair MN system...
  • Page 25: Information On Positioning Of The Components Of The Optional Reverse Osmosis System Condair Ro-Hb

    Ensure sufficient space (min. 11.8" Net weight: 29.3 lbs (13.3 kg) (min. 300 mm)) to position the drain Operating weight: 34.2 lbs (15.5 kg) funnel with trap Fig. 11: Dimensions RO-H (dimensions in inch (mm)) Planning a Condair MN system...
  • Page 26 1.77" (45) 7.87" (200) 3.94" (100) 9.84" (250) 0.22" (8.5) Weight booster module "Single": 18.7 lbs (8.5 kg) Weight booster module "Multiple": 19.8 lbs (9.0 kg) Fig. 13: Dimensions booster module (dimensions in inch (mm)) Planning a Condair MN system...
  • Page 27 If possible, the RO-HB reverse osmosis system, the booster module(s) as well as the central unit(s) and the water filter(s) of the Condair MN should be placed on the same floor. If this is not possible in your specific case, please contact your Condair representative.
  • Page 28 1.77" (45) 1.77" (45) Booster Water filter Central unit module 3.94" (100) Reverse osmosis unit Condair RO-H Flow tank 13.78" (350) 1.77" (45) Free space Fig. 16: Placement example 3 single system (dimensions in inch (mm)) Planning a Condair MN system...
  • Page 29 3.94" (100) 1.77" (45) Free space Important note: In the case of multiple systems, only MN systems with one water filter can be used or connected! Fig. 17: Placement example multiple system (dimensions in inch (mm)) Planning a Condair MN system...
  • Page 30: Positioning The Humidifier Units

    – Humidifier units should ideally be positioned in walkways. However, it must be ensured that people are not negatively impacted by the cooling of the room air during atomization. Planning a Condair MN system...
  • Page 31: Water Supply Requirements

    4.8.2 Water supply requirements for the reverse osmosis system Condair RO-HB Information on the water supply of the reverse osmosis system Condair RO-HB can be found in the separate installation and operation manual for the Condair RO-H. Planning a Condair MN system...
  • Page 32: Water Outlet Requirements

    Note: If the water drain of the optional reverse osmosis unit Condair RO-H cannot be routed into the drain funnel of the central unit, an additional drain funnel with trap must be provided in the room.
  • Page 33: Lan Connection Requirements

    To ensure hygienic operation the Condair MD system must be serviced by authorized service special- ists once a year. The service is regulated in a corresponding service contract. Condair arranges and carries out the annual service. After completion, the service must be documented in the customer's service log.
  • Page 34: Delivery Scope Overview

    4.13 Delivery scope overview All material not supplied by Condair must be arranged by the installer according to the conditions on site. Material Condair delivery Provided on site scope Central unit – Central unit with water filter(s) – Mains power cable (3-pin) with plug –...
  • Page 35: Preparatory Installations

    5.1.2 Storage and transport Storage The Condair MN components must be stored in the original packaging in a place secured against drip- ping water under the following conditions until installation: – Room temperature: 41 ... 104°F (5 ... 40°C) –...
  • Page 36: Tools Required For Installation

    Tools required for installation The following tools are required to install the Condair MN: – Standard electrical installation tools: – Pliers – Wire strippers (e.g. Weidmüller Stripex) – Crimping pliers (e.g. Knipex 975314) – Slot and Philips screwdrivers – Wire insertion tool –...
  • Page 37: Preparatory Installations Overview

    Preparatory installations overview The preparatory installations must be carried out by the electrician and plumber and consist of the fol- lowing tasks: Step Task Responsible Discussing the electrical plan with the installers Designers Carrying out preparatory installations. Electricians • Preparatory installations for flush-mounting humidifier units in new buildings with concrete ceilings: •...
  • Page 38 (see Section 5.7). • If applicable: Mount components of the optional reverse osmosis system Condair RO-HB at the intended location (see Section 5.8) • Install the drain funnel with trap beneath the central unit and, if designed as such, beneath the peripheral drain module(s) and...
  • Page 39: Preparatory Installations For Flush-Mounting Humidifier Units In New Buildings With Concrete Ceilings

    Preparatory installations for flush-mounting humidifier units in new build- ings with concrete ceilings 5.4.1 Install installation boxes for flush-mounting in concrete ceilings For flush-mounting humidifier units in concrete ceilings in new buildings or suspended insulated ceilings, the installation boxes must be installed at the intended humidifier unit installation points. 5.4.1.1 Flush-mounting installation boxes for concrete ceilings Use: for installation in concrete ceilings in new buildings...
  • Page 40: Laying The Guide Pipes

    5.4.2 Laying the guide pipes Lead a guide pipe (with feed-in cord/wire) into and away from each flush-mounting installation box and/ or to each installation point. The plan sets out the sequence in which the individual flush-mounting instal- lation boxes and/or installation points should be connected with guide pipes. The guide pipe running away from the last installation box and/or installation point for each spray circuit leads either back to the central unit (central spray circuit drainage) or the drain module (peripheral spray circuit drainage).
  • Page 41 Room 2 Room 3 Room 4 Room 1 Room 2 Room 3 Zone 5 Zone 3 Zone 2 Zone 4 Room 1 Room 4 Bathroom Kitchen Kitchen Bathroom Zone 1 Zone 6 1x CAN bus cable 1x hose Guide pipe ø0.98"...
  • Page 42 Room 2 Room 3 Room 4 Room 1 Room 2 Room 3 Zone 5 Zone 3 Zone 2 Zone 4 Room 1 Room 4 Bathroom Kitchen Kitchen Bathroom Zone 1 Zone 6 1x CAN bus cable 1x hose Guide pipe ø0.98"...
  • Page 43: Drilling Installation Openings In The Installation Boxes

    5.4.3 Drilling installation openings in the installation boxes • Once the casings are removed, the installation openings ø2.95" (ø75 mm) must be drilled in the lid of the installation boxes. ø2.95" ±0.04" (ø75 ±1 mm) Drill installation opening once casing is removed Fig.
  • Page 44: Preparatory Installations For Flush-Mounting Humidifier Units In Suspended Ceilings

    Preparatory installations for flush-mounting humidifier units in suspended ceilings 5.5.1 Drill installation openings in the suspended ceilings • Drill installation openings ø2.95" (ø75 mm) in the planned positions on the suspended ceilings. 5 7 " . 1 . m i n i n .
  • Page 45: Preparatory Installations For Surface-Mounting Humidifier Units

    Preparatory installations for surface-mounting humidifier units 5.6.1 Drill wall duct(s) If the hoses and CAN bus cable should be led through the wall during surface mounting, a wall duct 60 mm in diameter must be drilled into the intended installation point(s). "...
  • Page 46: Laying Cable Ducts

    5.6.2 Laying cable ducts Laying cable ducts depends on the cable duct used. In all cases, the cable duct must be selected so that a CAN bus cable and a hose can be led in and out of every surface mounting box. A cable duct must feed into and away from every installation point on the humidifier unit.
  • Page 47: Installing The Central Unit And Water Filter(S) In The Housing

    Installing the central unit and water filter(s) in the housing Installation overview " 1 . 6 ( 4 0 6 " 8 . 6 Per water filter Central unit ( 2 2 5 " 3 . 3 Operating weight in lbs (kg) 29.3 lbs (13.3 kg) 31.8 lbs (14.4 kg) 2 "...
  • Page 48 Mounting procedure 1. Mark the attachment points "A" for the attachment rails at the desired position using a spirit level. 2. Fasten the attachment rails to the wall with 2-inch screws into 2 x 4 wood studs (or equivalent). Before tightening the screws, align the attachment rails horizontally using a spirit level. 3.
  • Page 49: Installing The Components Of The Optional Reverse Osmosis System Condair Ro-Hb

    Installing the components of the optional reverse osmosis system Condair RO-HB Mounting the Condair RO-H and the flow tank Mount the reverse osmosis unit Condair RO-H and flow tank at the desired location, observing the placement instructions (see 4.6) and the information in the separate installation and operating Section manual for the Condair RO-H.
  • Page 50: Setting Up Water Inlet And Outlet

    – We recommend installing a water stop hose in the feed line to the Condair MN central unit. – So the disinfection kit can be connected during maintenance and periodic water samples can be taken from the inlet water, the last 19.7"...
  • Page 51 – The maximum length of the outlet pipe, from device connection to drain funnel, should not exceed 6.56 ft (2 m). Longer outlet pipes are only permissible by agreement with Condair. – Ensure that the outlet pipe, drain funnel and siphon are easily accessible and correctly attached for monitoring and cleaning purposes.
  • Page 52: Water Installation Overview

    5.9.2 Water installation overview Water supply connector Water drain connector Stop valve Backflow preventer for fluid category 2 with integrated particle filter (provided on site) Pressure reduction valve for pressures >14.5 psig (>500 kPa) Open drain funnel with syphon Fig. 29: Water installation overview Preparatory installations...
  • Page 53: Installing A Drain Funnel With Trap For Peripheral Drain Module(S)

    Install the drain funnel with trap at the intended location. Attach the drain funnel so that it cannot shift during operation. Note: The peripheral drain module(s) will be installed by the Condair service technician during commis- sioning. Fig. 30: Installing a drain funnel with trap for peripheral drain module(s)
  • Page 54: Feeding In Hoses And Can Bus Cables

    5.9.4 Feeding in hoses and CAN bus cables CAUTION! Risk of contamination Before feeding in the hoses, the end of the hose must be sealed (e.g. with adhesive tape). Once the hoses are inserted, both ends of the hose must be sealed. Important: The hoses and CAN bus cable for connection to the central unit must be labelled to avoid mixing them up (e.g.
  • Page 55 For peripheral spray circuit drainage, according to the Fig. 32, the CAN bus cables and the hoses must be inserted between the central unit, the humidifier units and the drain module (guide pipe with a hose and CAN bus cable). Hose Guide pipes ø0.98"...
  • Page 56 Information – The hoses and CAN bus cables must be led a minimum of 11.81" (300 mm) from the ceiling or floor connection point before they are cut to length (see Fig. 33). CAUTION! Risk of contamination Once the hoses are inserted and cut to length, both ends of the hose must be sealed to prevent pollution (e.g.
  • Page 57: Technical Data

    41 ... 77 °F (5 ... 25 °C) Permissible inlet water conductivity 5 ...1000 µS/cm Water treatment Water filter (disposable mixed-bed resin cartridge), Optional reverse osmosis system Condair RO-HB UV lamp For water sterilization Central unit electrical connection Plug 115 VAC / 60 Hz...
  • Page 58: Humidifier Unit Technical Data

    Note: When running the guide pipe through a ceiling plenum or any air plenum, electric metallic (EMT) conduit is the required guide pipe material. Technical data optional reverse osmosis system Condair RO-HB See separate installation and operating manual for the Condair RO-H. Technical data...
  • Page 59 Warranty Condair Inc. and/or Condair Ltd. (hereinafter collectively referred to as THE COMPANY), warrant for a period of two years after installation or 30 months from manufacturer’s ship date, whichever date is earlier, that THE COMPANY’s manufactured and assembled products, not otherwise expressly warranted, are free from defects in material and workmanship.
  • Page 60 U.S.A. 835 Commerce Park Drive Ogdensburg, New York 13669 CANADA 2740 Fenton Road Ottawa, Ontario K1T 3T7 TEL: 1.866.667.8321 FAX: 613.822.7964 EMAIL: na.humilife@condair.com WEBSITE: www.condairhumilife.com...