Introduction; Type Vcp-Wr (Red Line Series) Ratings - Eaton Cutler-Hammer VCP-WR 18 Series Instructions For The Use, Operation And Maintenance

Red line vacuum circuit breaker elements
Hide thumbs Also See for Cutler-Hammer VCP-WR 18 Series:
Table of Contents

Advertisement

I.B. 8295A61H03
SECTION 1: INTRODUCTION
The purpose of this book is to provide instructions for
unpacking, storage, use, operation and maintenance of
Type VCP-WR Vacuum Circuit Breakers. VCP-WR is a
vacuum interrupting element designed for value added
construction. The VCP-WR Red Line family of circuit
breaker elements is comprised of three element types
(Series 18, Series 20 and Series 29). The nominal
widths are 18 inches for Series 18, 20 inches for Series
20 and 29 inches for Series 29. Any one of the three
available elements can be used as a retrofitting drawout
breaker when the customer provides and combines the
appropriate cell interface, truck, levering mechanism,
secondary connections, interlocks and other accessory
items with the VCP-WR element. VCP-WR elements
can also be used for fixed breaker applications with oth-
ers responsible for all required interfaces.

1-1 TYPE VCP-WR (RED LINE SERIES) RATINGS

Table 1.1 VCP-WR Ratings
Identification
Rated Values
Current
Rated
Contin-
uous
Current
at
60 Hz
Circuit
Breaker
Series
Type
Width
Amps
VCP-WR Vacuum Circuit Breaker
50 VCP-WR 250
18, 20, 29 1200
18, 20, 29 2000
29
3000
50 VCP-WR 350
20, 29
1200
20, 29
2000
29
3000
75 VCP-WR 500
18, 29
1200
18, 29
2000
29
3000
150 VCP-WR 500
18
600
18, 29
1200
18, 29
2000
29
3000
150 VCP-WR 750
18, 29
1200
18, 29
2000
29
3000
150 VCP-WR 1000
29
1200
29
2000
29
3000
150 VCP-WR 1500
29
1200
29
2000
29
3000
Effective 7/97
Nominal Nominal
Voltage
Rated
Voltage
3-Phase
Rated
Short
Class
MVA
Max.
Circuit
Class
Voltage
Current
(at
Rated
Max.
kV)
I
E
kV
MVA
kA rms
Class
Class
kV rms
29
4.16
250
4.76
41
4.16
350
4.76
33
7.2
500
8.25
18
13.8
500
15
28
13.8
750
15
37
13.8
1000
15
63
13.8
1600
15
or
1500
SATISFACTORY PERFORMANCE OF THESE
BREAKERS IS CONTINGENT UPON PROPER APPLI-
CATION, CORRECT INSTALLATION AND ADE-
QUATE MAINTENANCE. THIS INSTRUCTION BOOK
MUST BE CAREFULLY READ AND FOLLOWED IN
ORDER TO OBTAIN OPTIMUM PERFORMANCE FOR
LONG USEFUL LIFE OF THE CIRCUIT BREAKERS.
TYPE VCP-WR BREAKERS ARE PROTECTIVE
DEVICES, AS SUCH, THEY ARE MAXIMUM RATED
DEVICES. THEREFORE, THEY SHOULD NOT
UNDER ANY CIRCUMSTANCES BE APPLIED OUT-
SIDE THEIR NAMEPLATE RATINGS.
Insulation Level
Rated
Rated
Rated Withstand
Inter-
Voltage Test Voltage
rupting sible
Range
Time
Factor
Low
Fre-
Impulse
K
quencey
kV rms
kV Crest
Cycles
1.24
19
60
5
1.19
19
60
5
1.25
36
95
5
1.30
36
95
5
1.30
36
95
5
1.30
36
95
5
1.0
36
95
5
!
WARNING
Related Required Capabilities
Rated
Rated
Current Values
Permis-
Max.
Maxi-
3 Sec.
Voltage
mum
Short
Tripping
Divided
Sym.
Time
Delay
by K
Inter-
Current
rupting
Carrying
Capability Capability
K Times Rated
Short Circuit
Current
KI
Y
E/K
Sec.
kV rms
kA rms
kA rms
2
3.85
36
2
4.0
49
2
6.6
41
2
11.5
23
2
11.5
36
2
11.5
48
2
15.0
63
Page 1
Closing
and
Latching
Capability
(Momen-
tary)
2.7 K
Times
Rated
Short
Circuit
Current
kA Crest
36
97
49
132
41
111
23
62
36
97
48
130
63
170