Section 1 Introduction; Type W-Vac Breaker Ratings; Table 1.1 Type W-Vac Vacuum Circuit Breaker Ratings - Eaton Cutler-Hammer 36W-VAC25 Instructions For Installation, Operation And Maintenance

Vacuum circuit breakers
Hide thumbs Also See for Cutler-Hammer 36W-VAC25:
Table of Contents

Advertisement

I.B. 3A74499B
SECTION 1: INTRODUCTION
The purpose of this book is to provide instructions for
unpacking, storage, installation, operation and mainte-
nance of Type W-VAC Vacuum Circuit Breakers. Type
W-VAC is a horizontal drawout type removable inter-
rupting element design. It was designed specifically to
IEC 56 Standards for reliable performance, ease of
handing, and simplified maintenance. Type W-VAC can
be applied in both single tier or double tier switchgear
applications, with the basic breaker element applicable
to retrofitting. Reliable control and protection for medium
voltage equipment and circuits are achieved though the
use of Type W-VAC Vacuum Circuit Breakers.

1-1 TYPE W-VAC BREAKER RATINGS

Refer to Table 1.1

Table 1.1 Type W-VAC Vacuum Circuit Breaker Ratings

Circuit
Rated
Breaker
Voltage
Type
at
50-60HZ
kV
36W-VAC25
3.6
72W-VAC16
7.2
72W-VAC20
7.2
72W-VAC25
7.2
72W-VAC32
7.2
120W-VAC16
12
120W-VAC20
12
120W-VAC25
12
120W-VAC32
12
120W-VAC40
12
150W-VAC16
15
150W-VAC20
15
150W-VAC25
15
150W-VAC32
15
Effective 11/97
Frequency
Rated Short Circuit
Breaking Current
& Short Circuit
Duration
Hz
kA
50/60
25
50/60
16
50/60
20
50/60
25
50/60
31.5
50/60
16
50/60
20
50/60
25
50/60
31.5
50/60
40
60
16
60
20
60
25
60
31.5
SATISFACTORY PERFORMANCE OF THESE
BREAKERS IS CONTINGENT UP-ON PROPER
APPLICATION, CORRECT INSTALLATION AND
ADEQUATE MAINTENANCE. THIS INSTRUCTION
BOOK MUST BE CAREFULLY READ AND FOL-
LOWED IN ORDER TO OBTAIN OPTIMUM PERFOR-
MANCE FOR LONG USEFUL LIFE OF THE CIRCUIT
BREAKERS.
TYPE W-VAC BREAKERS ARE PROTECTIVE
DEVICES, AS SUCH, THEY ARE MAXIMUM RATED
DEVICES. THEREFORE, THEY SHOULD NOT
UNDER ANY CIRCUMSTANCES BE APPLIED OUT-
SIDE THEIR NAMEPLATE RATINGS.
Rated Insulation Level
Lighting
Power
Pulse
Frequency
Withstand
Withstand
Voltage
Voltage
Sec
kV
kV
3
40
10
3
60
20
3
60
20
3
60
20
3
60
20
3
75
28
3
75
28
3
75
28
3
75
28
3
75
28
3
95
36
3
95
36
3
95
36
3
95
36
!
WARNING
Rated
Rated Nominal Current
Short
Circuit
Making
Current
kA
(Peak) Amperes
63
630, 1250, 2000
40
630, 800, 1250
50
630, 800, 1250, 1600
63
630, 800, 1250, 1600, 2000
79
1250, 2000
40
630, 800, 1250
50
630, 800, 1250, 1600
63
630, 800, 1250, 1600, 2000
79
1250, 2000
100
1250, 2000
40
630, 800, 1250
50
630, 800, 1250, 1600
63
630, 800, 1250, 1600, 2000
79
1250, 2000
Page 1