RDZ CHR 200-FC Technical Installation Manual page 19

Air handling units
Table of Contents

Advertisement

Descriptions
C-
signal - CAN port
C+
signal + CAN port
B
signal - RS-485 MODBUS master/slave port
A
signal + RS-485 MODBUS master/slave port
GND reference (GND)
ITB
INTRABUS port data
5V
ratiometric transducer power supply 0-5 V (5 VDC)
12V auxiliary power supply (12 VDC)
GND reference (GND)
analogue input (for NTC probes, 0-5 V, 0-10 V, 0-20 mA or
M1
4-20 mA transd.); AI1 can be configured also for dry contact
digital input; DI5
analogue input (for NTC probes, 0-5 V, 0-10 V, 0-20 mA or
M2
4-20 mA transd.); AI2 can be configured also for dry contact
digital input; DI6
analogue input (for NTC probes, 0-5 V, 0-10 V, 0-20 mA or
M3
4-20 mA transd.); AI3 can be configured also for dry contact
digital input; DI7
analogue input (for PTC, NTC or Pt 1000 probes); AI4 can be
M4
configured also for dry contact digital input; DI8
analogue input (for PTC, NTC or Pt 1000 probes); AI5 can be
M5
configured also for dry contact digital input; DI9
analogue input (for PTC, NTC or Pt 1000 probes); AI6 can be
M6
configured also for dry contact digital input; DI10
analogue input (for PTC, NTC or Pt 1000 probes); AI7 can be
M7
configured also for dry contact digital input; DI11
M8
digital input (dry contact and for pulse trains up to 2 KHz); DI3
M9
digital input (dry contact and for pulse trains up to 2 KHz); DI4
AO1 analogue output 1 (for 0-10 V or PWM)
AO2 analogue output 2 (for 0-10 V or PWM)
AO3 analogue output 3 (for 0-10 V or PWM)
AO4 analogue output 4 (for 0-10 V or PWM)
PS
device power supply (115... 230 VAC)
PS
device power supply (115... 230 VAC)
HV2 high voltage digital input; DI2
HV2 high voltage digital input; DI2
HV1 high voltage digital input; DI1
HV1 high voltage digital input; DI1
NC6 K6 digital output normally closed contact
C6
K6 digital output common contact
NO6 K6 digital output normally open contact (16 A res. @ 250 VAC)
NO5 K5 digital output normally open contact (8 A res. @ 250 VAC) contatto normalmente aperto uscita digitale K5 (8 A res. @ 250 VAC)
C5
K5 digital output common contact
NO4 K4 digital output normally open contact (5 A res. @ 250 VAC) contatto normalmente aperto uscita digitale K4 (5 A res. @ 250 VAC)
C4
K4 digital output common contact
NO3 K3 digital output normally open contact (5 A res. @ 250 VAC) contatto normalmente aperto uscita digitale K3 (5 A res. @ 250 VAC)
C3
K3 digital output common contact
NO2 K2 digital output normally open contact (5 A res. @ 250 VAC) contatto normalmente aperto uscita digitale K2 (5 A res. @ 250 VAC)
C2
K2 digital output common contact
NO1 K1 digital output normally open contact (5 A res. @ 250 VAC) contatto normalmente aperto uscita digitale K1 (5 A res. @ 250 VAC)
C1
K1 digital output common contact
Descrizione
segnale - porta CAN
segnale + porta CAN
segnale - porta RS-485 MODBUS master/slave
segnale + porta RS-485 MODBUS master/slave
riferimento (GND)
data porta INTRABUS
alimentazione trasduttori raziometrici 0-5 V (5 VDC)
alimentazione ausiliaria (12 VDC)
riferimento (GND)
ingresso analogico (per sonde NTC, trasd. 0-5 V, 0-10 V, 0-20 mA o
4-20 Ma); AI1 configurabile anche per ingresso digitale a contatto
pulito; DI5
ingresso analogico (per sonde NTC, trasd. 0-5 V, 0-10 V, 0-20 mA o
4-20 Ma); AI2 configurabile anche per ingresso digitale a contatto
pulito; DI6
ingresso analogico (per sonde NTC, trasd. 0-5 V, 0-10 V, 0-20 mA o
4-20 Ma); AI3 configurabile anche per ingresso digitale a contatto
pulito; DI7
ingresso analogico (per sonde PTC, NTC o Pt 1000) AI4 configurabile
anche per ingresso digitale a contatto pulito; DI8
ingresso analogico (per sonde PTC, NTC o Pt 1000) AI5 configurabile
anche per ingresso digitale a contatto pulito; DI9
ingresso analogico (per sonde PTC, NTC o Pt 1000) AI6 configurabile
anche per ingresso digitale a contatto pulito; DI10
ingresso analogico (per sonde PTC, NTC o Pt 1000) AI7 configurabile
anche per ingresso digitale a contatto pulito; DI11
ingresso digitale (a contatto pulito e per treni di impulsi fino a 2
KHz); DI3
ingresso digitale (a contatto pulito e per treni di impulsi fino a 2
KHz); DI4
uscita analogica 1 (per segnale 0-10 V o PWM)
uscita analogica 2 (per segnale 0-10 V o PWM)
uscita analogica 3 (per segnale 0-10 V o PWM)
uscita analogica 4 (per segnale 0-10 V o PWM)
alimentazione dispositivo (115... 230 VAC)
alimentazione dispositivo (115... 230 VAC)
ingresso digitale in alta tensione; DI2
ingresso digitale in alta tensione; DI2
ingresso digitale in alta tensione; DI1
ingresso digitale in alta tensione; DI1
contatto normalmente chiuso uscita digitale K6
contatto comune uscita digitale K6
contatto normalmente aperto uscita digitale K6 (16 A res. @ 250
VAC)
contatto comune uscita digitale K5
contatto comune uscita digitale K4
contatto comune uscita digitale K3
contatto comune uscita digitale K2
contatto comune uscita digitale K1
19

Advertisement

Table of Contents
loading

Table of Contents