Descriptions
C-
signal - CAN port
C+
signal + CAN port
B
signal - RS-485 MODBUS master/slave port
A
signal + RS-485 MODBUS master/slave port
GND reference (GND)
ITB
INTRABUS port data
5V
ratiometric transducer power supply 0-5 V (5 VDC)
12V auxiliary power supply (12 VDC)
GND reference (GND)
analogue input (for NTC probes, 0-5 V, 0-10 V, 0-20 mA or
M1
4-20 mA transd.); AI1 can be configured also for dry contact
digital input; DI5
analogue input (for NTC probes, 0-5 V, 0-10 V, 0-20 mA or
M2
4-20 mA transd.); AI2 can be configured also for dry contact
digital input; DI6
analogue input (for NTC probes, 0-5 V, 0-10 V, 0-20 mA or
M3
4-20 mA transd.); AI3 can be configured also for dry contact
digital input; DI7
analogue input (for PTC, NTC or Pt 1000 probes); AI4 can be
M4
configured also for dry contact digital input; DI8
analogue input (for PTC, NTC or Pt 1000 probes); AI5 can be
M5
configured also for dry contact digital input; DI9
analogue input (for PTC, NTC or Pt 1000 probes); AI6 can be
M6
configured also for dry contact digital input; DI10
analogue input (for PTC, NTC or Pt 1000 probes); AI7 can be
M7
configured also for dry contact digital input; DI11
M8
digital input (dry contact and for pulse trains up to 2 KHz); DI3
M9
digital input (dry contact and for pulse trains up to 2 KHz); DI4
AO1 analogue output 1 (for 0-10 V or PWM)
AO2 analogue output 2 (for 0-10 V or PWM)
AO3 analogue output 3 (for 0-10 V or PWM)
AO4 analogue output 4 (for 0-10 V or PWM)
PS
device power supply (115... 230 VAC)
PS
device power supply (115... 230 VAC)
HV2 high voltage digital input; DI2
HV2 high voltage digital input; DI2
HV1 high voltage digital input; DI1
HV1 high voltage digital input; DI1
NC6 K6 digital output normally closed contact
C6
K6 digital output common contact
NO6 K6 digital output normally open contact (16 A res. @ 250 VAC)
NO5 K5 digital output normally open contact (8 A res. @ 250 VAC) contatto normalmente aperto uscita digitale K5 (8 A res. @ 250 VAC)
C5
K5 digital output common contact
NO4 K4 digital output normally open contact (5 A res. @ 250 VAC) contatto normalmente aperto uscita digitale K4 (5 A res. @ 250 VAC)
C4
K4 digital output common contact
NO3 K3 digital output normally open contact (5 A res. @ 250 VAC) contatto normalmente aperto uscita digitale K3 (5 A res. @ 250 VAC)
C3
K3 digital output common contact
NO2 K2 digital output normally open contact (5 A res. @ 250 VAC) contatto normalmente aperto uscita digitale K2 (5 A res. @ 250 VAC)
C2
K2 digital output common contact
NO1 K1 digital output normally open contact (5 A res. @ 250 VAC) contatto normalmente aperto uscita digitale K1 (5 A res. @ 250 VAC)
C1
K1 digital output common contact
Descrizione
segnale - porta CAN
segnale + porta CAN
segnale - porta RS-485 MODBUS master/slave
segnale + porta RS-485 MODBUS master/slave
riferimento (GND)
data porta INTRABUS
alimentazione trasduttori raziometrici 0-5 V (5 VDC)
alimentazione ausiliaria (12 VDC)
riferimento (GND)
ingresso analogico (per sonde NTC, trasd. 0-5 V, 0-10 V, 0-20 mA o
4-20 Ma); AI1 configurabile anche per ingresso digitale a contatto
pulito; DI5
ingresso analogico (per sonde NTC, trasd. 0-5 V, 0-10 V, 0-20 mA o
4-20 Ma); AI2 configurabile anche per ingresso digitale a contatto
pulito; DI6
ingresso analogico (per sonde NTC, trasd. 0-5 V, 0-10 V, 0-20 mA o
4-20 Ma); AI3 configurabile anche per ingresso digitale a contatto
pulito; DI7
ingresso analogico (per sonde PTC, NTC o Pt 1000) AI4 configurabile
anche per ingresso digitale a contatto pulito; DI8
ingresso analogico (per sonde PTC, NTC o Pt 1000) AI5 configurabile
anche per ingresso digitale a contatto pulito; DI9
ingresso analogico (per sonde PTC, NTC o Pt 1000) AI6 configurabile
anche per ingresso digitale a contatto pulito; DI10
ingresso analogico (per sonde PTC, NTC o Pt 1000) AI7 configurabile
anche per ingresso digitale a contatto pulito; DI11
ingresso digitale (a contatto pulito e per treni di impulsi fino a 2
KHz); DI3
ingresso digitale (a contatto pulito e per treni di impulsi fino a 2
KHz); DI4
uscita analogica 1 (per segnale 0-10 V o PWM)
uscita analogica 2 (per segnale 0-10 V o PWM)
uscita analogica 3 (per segnale 0-10 V o PWM)
uscita analogica 4 (per segnale 0-10 V o PWM)
alimentazione dispositivo (115... 230 VAC)
alimentazione dispositivo (115... 230 VAC)
ingresso digitale in alta tensione; DI2
ingresso digitale in alta tensione; DI2
ingresso digitale in alta tensione; DI1
ingresso digitale in alta tensione; DI1
contatto normalmente chiuso uscita digitale K6
contatto comune uscita digitale K6
contatto normalmente aperto uscita digitale K6 (16 A res. @ 250
VAC)
contatto comune uscita digitale K5
contatto comune uscita digitale K4
contatto comune uscita digitale K3
contatto comune uscita digitale K2
contatto comune uscita digitale K1
19