Pin Assignment; Requirements And Connection To Evaluation Devices - Pilz PSEN ma1.1p-12 Operating Manual

Table of Contents

Advertisement

PSEN ma1.1p-12
}
In the following cases, check the function that detects shorts across contacts prior to
commissioning:
– On evaluation devices with DC supply voltage: Overall cable resistance ≥ 15 Ohms
– On evaluation devices with AC supply voltage: Overall cable resistance ≥ 25 Ohms
– For details of how to perform the test for shorts across the contacts, please refer to

Pin assignment

The safety switch is shown in an unoperated condition.
Assignment of
the 4-pin con-
nector

Requirements and connection to evaluation devices

For use of PSEN ma1.1p-12 in accordance with DIN EN 60947-5-3 an evaluation device
must be connected.
Connect the PSEN ma1.1p-12
}
either with a certified Pilz evaluation device
}
or with an evaluation device with defined properties
Certified Pilz evaluation devices are, for example:
}
PNOZelog for safety gate monitoring
– PNOZ e1p, PNOZ e1.1p, PNOZ e1vp
– PNOZ e5.11p
– PNOZ e6vp, PNOZ e6.1p
}
PNOZpower for safety gate monitoring
– PNOZ p1p, PNOZ p1vp
}
PNOZsigma for safety gate monitoring
– PNOZ s3
– PNOZ s4
– PNOZ s5
Operating Manual PSEN ma1.1p-12
22190-EN-04
per channel
per channel
the operating manual for the relevant evaluation device.
NOTICE
The colour marking for the connection lead only applies for the cable that
Pilz supplies as an accessory
1
3
brown
[1]
2
white
[2]
blue
[3]
4
black
[4]
| 10