Maintenance
10.7 Remove and Replace
Figure 10-13
To remove the filter media, simply pull it away from the frame.
Replacing Filter Media
• After replacing the filter media, carefully place and align the filter cover to the filter frame that
is attached to the VFD.
• Gently push the filter cover onto the frame to latch it in place.
Cleaning the Filter
• Depending on the type of contamination, shake the dust from the filter, vacuum clean them
or wash them. If the filter is highly contaminated, dispose of it properly, and replace the filter.
Note
Do not use pressurized equipment to clean the filters in the door!
The filter mats are made of polyester fiber and must not be cleaned using pressurized equipment
(e.g. with water jet or compressed air), since this can damage the filter mats and render them
ineffective.
Note
Drives with M58 option code do not have filters.
See heat exchanger section.