10.6 Cleaning

10.6
Cleaning
10.6.1

Contact for Cleaning Measures

If contamination occurs, contact Siemens customer service. Refer to the appendix "Service and
Support".
10.6.2

Removing Dust Deposits

Dust Deposits
Dust deposits inside the cabinet unit must be removed at regular intervals (or at least once a
year) by qualified personnel in accordance with the relevant safety regulations.
• Use only a soft bristle, anti-static brush to loosen the dust particles.
• Do not use a vacuum cleaner directly on components.
• Only use dry compressed air (maximum 1 bar) from a distance no less than 6 inches from
components.