Address Status; Description Of Status - Siemens SIMATIC ET 200SP CM 1xDALI Programming Manual

Hide thumbs Also See for SIMATIC ET 200SP CM 1xDALI:
Table of Contents

Advertisement

CM 1xDALI command list
3.7 Return code and control status
3.7.2

Address status

Error code
16#00
16#01
16#02
16#03
16#04
16#05
16#0F
3.7.3

Description of status

Control gear status
Bit
0
1
2
3
4
5
6
7
Control gear type related status
Bit
0
1
2
3
4
52
Description
Status is unknown. Query or scan the DALI bus.
If this short address is configured, the device with this short address is the same
as configured. If this short address is not configured, a device with this address is
present on the DALI bus.
No device with this short address is on the DALI bus.
More than one device with this short address is on the DALI bus.
The configured type is not the type of the actual device on the DALI bus.
The configured number of instances does not correspond to the actual device.
Only input devices have this status.
This short address is assigned to DALI module itself.
Description
Control gear failure
Lamp failure
Lamp on
Limit error
Fade running
Reset state
No short address
Power cycle seen
Type 1 (emergency)
Type 2 (discharge)
Circuit failure
Mains voltage too low
Battery duration fail-
Mains voltage too
ure
high
Batter failure
Converter thermal
overload
Emergency lamp
Reserved
failure
Function test maxi-
Ignition time out
mum delay exceeded
Type 3 (halogen)
Short circuit
Open circuit
Load decrease
Load increase
Current protector
active
ET 200SP CM 1xDALI Communication Model Description
Programming Manual, 12/2019, A5E47581955-AA
type 4 (incandescent)
Load over-current
shutdown
Open circuit
Load decrease
Load increase
Reserved