Query Control Gear Operating Hours; Set Control Gear Operating Hours - Siemens SIMATIC ET 200SP CM 1xDALI Programming Manual

Hide thumbs Also See for SIMATIC ET 200SP CM 1xDALI:
Table of Contents

Advertisement

3.3.3

Query control gear operating hours

Description
Command ID 13
Input Param-
eters
Response
Parameters
Comment
3.3.4

Set control gear operating hours

Description
Command ID 14
Input Param-
eters
Response
Parameters
ET 200SP CM 1xDALI Communication Model Description
Programming Manual, 12/2019, A5E47581955-AA
Use this CM command to query the operating hours of a control gear. The operating
hours accumulate when the control gear remains on for one hour. The operating
hours are stored in the CM 1xDALI. If you change short addresses of two control
gears, the operating hours of these two control gears are not be changed.
With "Start upload control gear parameters (Page 41)", you can exchange the related
operating hours of these two control gears.
Before calling this command, configure the control gear using the "Add control gear
(Page 32)" instruction or the "Start upload control gear parameters (Page 41)" instruc-
tion.
Byte 0
Short address
Byte 0
Return code (Page 51)
16#8D (if the control gear is not configured)
16#8B (if the type of control gear is mismatched)
Byte 1
Low byte of the operating hours.
Byte 2
High byte of the operating hours.
When the actual level of the control gears is not 0, the operating hours accumulate.
The CM 1xDALI checks the actual level every 10 minutes.
Use this CM command to set the operating hours of a control gear. The operating
hours accumulate when the control gear remains on for one hour. The operating
hours are stored in the CM 1xDALI.
Before calling this function block, make sure that the control gear is configured by
using the "Add control gear (Page 32)" instruction and the "Start upload control gear
parameters (Page 41)" instruction.
Reset the operating hours after exchanging the physical control gear device.
Byte 0
Short address
Byte 1
Low byte of the operating hours.
Byte 2
High byte of the operating hours.
Byte 0
Return code (Page 51)
When you set the operating hours of the control gears, the following
occurs:
If the control gear is not configured, the error code in the response
is 16#8D.
If the control gear is configured, but the type of control gear is
mismatched, the error code in the response is 16#8B.
CM 1xDALI command list
3.3 Diagnostic
29

Advertisement

Table of Contents
loading

Table of Contents