Remove Control Gear Scene; Start Download Control Gear Parameters; Start Upload Control Gear Parameters - Siemens SIMATIC ET 200SP CM 1xDALI Programming Manual

Hide thumbs Also See for SIMATIC ET 200SP CM 1xDALI:
Table of Contents

Advertisement

3.4.12

Remove control gear scene

Description
Command ID 32
Input Param-
eters
Response
Parameters
3.4.13

Start download control gear parameters

Description
Command ID 33
Input Param-
eters
Response
Parameters
3.4.14

Start upload control gear parameters

Description
Command ID 34
Input Param-
eters
Response
Parameters
ET 200SP CM 1xDALI Communication Model Description
Programming Manual, 12/2019, A5E47581955-AA
Use this CM command to remove the scene configuration of a control gear.
This command has the same behavior as calling "Set control gear scene (Page 40)"
when scene level is 255 (16#FF).
Byte 0
Short address of the control gear
Byte 1
Scene number
Byte 0
Return code (Page 51)
Use this CM command to send the parameters saved in the CM 1xDALI to the physi-
cal device.
The CM 1xDALI provides a response to the CPU when the procedure is started. You
can check the progress and result of the procedure by "querying the current com-
mand progress (Page 49)".
Byte 0
Short address of the device
Byte 0
Return code (Page 51)
Use this CM command to query the parameters of the physical device, and save them
in CM 1xDALI.
The CM 1xDALI sends a response to the CPU when it starts the procedure. You can
check the progress and result of the procedure by "querying the current command
progress (Page 49)".
Byte 0
Short address
Byte 0
Return code (Page 51)
CM 1xDALI command list
3.4 Configuration
41

Advertisement

Table of Contents
loading