How To Do A Master Reset; Master Reset; Individual Parameter Reset; Fault Reset - Siemens Sitrans LR 460 Instruction Manual

Hide thumbs Also See for Sitrans LR 460:
Table of Contents

Advertisement

How to do a Master Reset

Master Reset

Following a Master Reset, complete reprogramming is required.
Note:
2506
Values
2712
32768
Example: do a Profile reset
1.
Go to Reset:
1. Identification Menu
1. 2. Configuration
2.
Press the Right ARROW key
3.
Key in 1 (Profile Reset) to reset all parameters except PROFIBUS address.
4.
Press the Right ARROW key
Navigation mode.

Individual Parameter Reset

1.
Press Right ARROW
2.
The value returns to the default factory setting.

Fault Reset

Used to reset a fault message after an active fault has occurred and been corrected. A
manual reset is required only for certain faults, identified by an asterisk (*) in the General
Fault Code list on page 51.
To reset, key in the value of the fault code in question.
1.
Go to Reset Fault:
I
1.
dentification Menu
1. 2. Configuration
2.
Press the Right ARROW key
3.
Key in the number of the Fault Code to reset the status to normal operation.
1.
Manufacturer's settings:
AIFB Filter Time Constant = 10 s
LTB values set for 0 - 20 m (Low and High Calibration points; Near Range and Far Range)
7ML19985JM01
Reset all parameters (except PROFIBUS address) to PROFIBUS PA profile
1
default values
Warm Start: restart the device (this option is rarely used)
Reset PROFIBUS address to 126
Reset to manufacturer's default values (factory settings)
1.2.3. Reset
to open Edit mode.
again, to accept the changes and return to
1
, then CLEAR
1.2.4. Reset Fault
to open Edit mode.
SITRANS LR 460 – INSTRUCTION MANUAL
, then Right ARROW
C
1
.
Page 35