3.7.4. Maximum Output Value - AIFB1
The maximum recorded Output Value from the Analog Input Function Block 1.
3.7.5. Minimum Output Value - AIFB2
The minimum recorded Output Value from the Analog Input Function Block 2.
3.7.6. Maximum Output Value - AIFB2
The maximum recorded Output Value from the Analog Input Function Block 2.
4. Service
Note: Default settings in the parameter tables are indicated with an asterisk (*)
unless explicitly stated.
4.1. Master Reset
Following a Factory Reset, some degree of reprogramming may be required,
Note:
depending on the option chosen below.
Reset
Options
Factory Defaults
Standard
Defaults
Informational
Functional
Warm Start
Reset Address to
126
To access via SIMATIC PDM:
Open the menu Device – Master Reset. For more detail see
57.
7ML19985JF04
SITRANS LR250 (PROFIBUS PA) – OPERATING INSTRUCTIONS
Result
Resets all user parameters to the manufacturer's default settings, with
certain exceptions. The list of exceptions includes, but is not limited to:
•
Tag
•
Message
•
Descriptor
•
Installation Data
•
Device Address
•
Write Protection
•
Auto False Echo Suppression Range
•
learned TVT
Resets all resettable parameters excluding device addresses to the PRO-
FIBUS standard default settings.
Resets parameters such as Tag and Descriptor.
Resets parameters that control device behavior and functionality (such as
calibration points)
Has the same effect as recycling power to the device
Resets the PROFIBUS device address to 126
If the address lock was on, will disable the lock.