E T C I n s t a l l a t i o n G u i d e
SimpleTap Cubicle Station
Preparation
The SimpleTap Cubicle Station can be mounted on any surface such as a wall,
cubicle, or desk. The station should be installed in the room where the Aero
controllers are controlling the light fixtures or circuits. Consideration should be
made for locating the controllers, switches, and sensors based on the
construction materials in the space and furniture that may disrupt the
transmissions. Installation should follow local codes and standard practices.
It is recommended that stations and sensors be placed with in 50 feet (15m) of
the controller for optimal performance.
Material
Line of sight
Line of sight
Plasterboard
Brick
Concrete
FerroConcrete
Ceiling
Material
Wood/Plaster/Glass
Brick/MDF
Metal
Installing the SimpleTap Cubicle Station
The SimpleTap Cubicle Station can be surface mounted using double-sided
tape, or Velcro
The occupancy sensor is a passive infrared (PIR) sensor and is designed for
small areas like an office or cubicle space. The sensors range is cone shaped,
6.5 feet (2m) long from the sensor and 8 feet (2.5m) in diameter. Within this
range, most motions will trigger an occupied state.
Sim pl eT ap Cub ic le St at i on
Typical Radio Range
Range - typical
100 feet (30m) corridors
330 feet (100m) open halls
100 feet (30m) through 5 walls
65 feet (20m) through 3 walls
65 feet (20m) through 3 walls
33 feet (10m)
1 ceiling
Signal Loss
Attenuation
0-10%
5-35%
90-100%
®
. Mounting hardware or tape is not supplied.