SMC Networks HRR010-A-10 Series Operation Manual page 125

Thermo-chiller
Hide thumbs Also See for HRR010-A-10 Series:
Table of Contents

Advertisement

Alarm
Description
No.
AL01
Low level in tank
AL02
Low level in tank
6
AL04
Water leakage
8
AL05
Pump inverter error
9
AL06
Internal fan stop
Circulating fluid discharge
AL09
pressure rise
7
AL10
Flow rate decreased
Ambient temperature is
AL11
3
out of the range
Electric conductivity
AL12
4
increase
AL13
NOT TEMP READY
Circulating fluid
AL14
temperature increase
Circulating fluid
AL15
temperature decrease
7
AL17
Low flow rate
High circulating fluid
AL18
discharge temp.
High circulating fluid
AL19
return temp.
High circulating fluid
AL21
discharge pressure
Low circulating fluid
AL22
discharge pressure
AL24
Memory error
Contact input 1
AL25
signal detection
Contact input 2
AL26
signal detection
AL27
Forced stop
AL28
Notice for maintenance
AL29
Communication error
AL30
Compressor circuit error
AL31
Sensor error
AL32
Controller error
1 Selectable from OFF / WRN / FLT
* 2 Selectable from WRN / FLT
3 Only air-cooled type can be set
4 Option DM 【With electric conductivity control function , DI water (pure water) piping】 only. When
entering the range, the alarm is released automatically.
5 Selectable from OFF / WRN
6 Not generated for option Z.
7 Not generated for options Z and Z1.
8 For option T1.
9 For water-cooled type.
HRR Series
Table 7-1 Alarm code list and Troubleshooting
Display unit
Initial value
Upper stage
Lower stage
(White)
FLT
AL01
LOW⇒LEVEL⇒FLT
WRN
AL02
LOW⇒LEVEL⇒WRN
1
WATER ⇒ LEAK
AL04
WRN
PUMP ⇒ INV
WRN
AL05
FAN ⇒ ERROR
WRN
AL06
2
HIGH ⇒ PRESS
AL09
FLT
1
AL10
LOW⇒FLOW⇒WRN
WRN
1
AL11
AMB⇒TEMP⇒OUT
OFF
5
DI ⇒ ERROR
AL12
WRN
1
AL13
TEMP⇒READY⇒ERROR
OFF
1
AL14
TEMP⇒OUT.HI
OFF
1
AL15
TEMP⇒OUT.LO
OFF
1
AL17
LOW⇒FLOW⇒FLT
FLT
TEMP ⇒ FLT
FLT
AL18
FLT
AL19
RET⇒TEMP⇒FLT
FLT
AL21
HIGH⇒PRESS⇒FLT
FLT
AL22
LOW⇒PRESS⇒FLT
MEM ⇒ ERROR
FLT
AL24
1
INP1 ⇒ ERROR
AL25
FLT
1
AL26
INP2 ⇒ ERROR
FLT
FORCE ⇒ STOP
FLT
AL27
1
MANT ⇒ ALARM
AL28
OFF
1
COMM ⇒ ERROR
AL29
WRN
FLT
AL30
REF⇒ERROR⇒0000
FLT
AL31
SENS⇒ERROR⇒0000
FLT
AL32
CTRL⇒ERROR⇒0000
Chapter 7 Alarm Notification and Troubleshooting
(Press the reset key after eliminating the cause.)
(Green)
Fluid level shown by the fluid level meter has fallen.
Add circulating fluid.
Circulating fluid leakage inside the unit is suspected.
Check the installation environment. Clean the dust filter of the
ventilation.
Check for fan rotation.
Piping resistance increased. Check the opening of the valve,
pinching or blockage of the piping or clogging of the filter.
Check the installation environment. Clean the dust filter of the
ventilation.
Replace DI filter.
Overloaded, cooling failure, insufficient circulating fluid flow rate,
large fluctuation of the heat load, etc.
Increase the flow rate through the chiller.
(Adjust the by-pass valve)
Displayed flow rate: 2LPM or less, piping is thin, external valve is
closed, pinching or blockage of the piping or clogging of the filter.
Discharge temp.: 45
insufficient flow rate, etc. Increase the flow rate through the chiller.
(Adjust the by-pass valve)
o
Return temp.: 45
etc. Increase the flow rate through the chiller.
(Adjust the by-pass valve)
Displayed pressure: 0.4MPa or higher. Connect piping so that the
pressure is 0.4MPa or less. Adjust the bypass valve.
Displayed pressure:0.03MPa or less.
Check that the pump has not stopped.
Turn off the power supply switch and restart.
If the error occurs again, ask for service.
Contact input has been detected.
Time for pump to continue operation is stopped (press
"RUN/STOP" key for 5 seconds).
Notice for maintenance, perform maintenance for part for which
alarm is generated.
No request message from the host computer.
Try to send the request message again.
Error occurred in the refrigerated circuit. Ask for service.
An error occurred in a sensor. Ask for service.
An error occurred in the controller. Ask for service.
HRX-OM-X084
Cause / Remedy
o
C or higher. Overload, cooling failure,
C or higher. Insufficient chiller flow rate, overload,
7.3 Trouble shooting