SMC Networks HRR010-A-10 Series Operation Manual page 27

Thermo-chiller
Hide thumbs Also See for HRR010-A-10 Series:
Table of Contents

Advertisement

The water cooled product radiates heat to the facility water.
It is necessary to supply the facility water. Please prepare the facility
water system that satisfies the heat radiation and the facility water
specifications below.
 Required facility water system (for water cooled type)
Model
Radiated
HRR010-W-10/20-
HRR Series
Facility water source to be prepared
Table 3-2
Heat
Facility water temp.
kW
Approx.2
(Rating 25)
Required facility water flow rate
range
o
C
5 to 35
HRX-OM-X084
Chapter 3 Transport and Setting Up
l/min
Facility water temprature
25℃
32℃
6
10
3.2 Installation
35℃
13
3-5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hrr010-a-20 seriesHrr010-w-10 seriesHrr010-w-20 series

Table of Contents