SMC Networks HRR010-A-10 Series Operation Manual page 94

Thermo-chiller
Hide thumbs Also See for HRR010-A-10 Series:
Table of Contents

Advertisement

HRX-OM-X084
Chapter 5 Display and Setting of Various Functions
Contact input signal 2 delay timer
24.
Press the [▼] key. Displays screen for setting the Contact input signal 2 detection
delay timer for reading.
Time for starting detection of the contact input signal 2 (sec) can be set.
●Setting range: 0 to 300sec. (Initial value: 0sec.)
Contact input signal 2 OFF detection time
25.
Press the [▼] key. Displays screen for setting the contact input signal 2 OFF detection
timer.
"Alarm AL26: Contact input signal 2 detection" is generated when the set time(sec) passed
from when the contact input signal 2 is not detected.
(When the signal is not detected for the set time, alarm is generated)
●Setting range: 0 to 10sec. (Initial value: 0sec.)
Switching of communication error alarm
26.
Press the [▼] key. Displays screen for setting the communication error alarm
operation.
Operation for alarm AL29: Communication error can be selected.
Set value
OFF
WRN
FLT
5.5 Advanced setting mode
5-42
Setting of the contact input signal 2 delay
timer for reading
SEC
INP2⇒ DELAY( Alternately displayed )
Contact input signal2 set value of the OFF
detection timer.
SEC
INP2 ⇒ OVER( Alternately displayed )
Operation for communication error alarm
COMM ⇒ ALARM( Alternately displayed )
Contents
Alarm is not generated.
Operation of this product will continue when the
alarm occurs.
Operation of this product will stop when the alarm
occurs.
Initial value