Circulating fluid flow display
5.
Press the [▼] key.
The circulating fluid flow rate is displayed on the digital display.
( Not displayed for options Z and Z1. )
RUN
Pump output set value display
6.
Press the [▼] key.
The inverter pump output set value is displayed on the digital display.
(Only for option T1 [Inverter pump]).
RUN
Press the [ENT] key, the pump output set value will blink and the set value can be
changed. Change the set value by pressing the [▼][▲] key.
After changing the set value, set it by pressing the [ENT] key.
After setting the value, blinking will end.
(The factory default : 90.0%)
Electric conductivity display
7.
Press the [▼] key.
The electric conductivity is displayed on the digital display.
(Only for option DM [Electric conductivity control function, DI water (pure water)
piping]) The unit is "μS / cm".
RUN
HRR Series
Circulating fluid flow
LPM
Pump output set value(setting range : 60.0 to 100.0%)
Electric conductivity
Chapter 5 Display and Setting of Various Functions
The display flow rate does not include
the circulating fluid flow rate flowing in
the bypass of this product.
HRX-OM-X084
5.4 Basic setting mode
5-13